AIR CONDITIONING
Fault finding - Introduction62A
V4
Manual air conditioning
and
Climate control
4. FAULT FINDING PROCEDURE
Check the battery charge and the
condition of the fuses
Print the system fault finding log
(available on CLIP and in the
Workshop Repair Manual or
Technical Note)
Connect CLIP
Dialogue with
Electronic Control
Unit?no
yes
Read the faults
no
Faults present
yes
Deal with present faults
Deal with stored faults
The cause is still
presentnoFault
solved
yes
See fault finding chart 1
Conformity check
The cause is still
presentnoFault
solved
Use fault finding charts (ALPs)
The cause is still
presentnoFault
solved
Contact Techline with the
completed fault finding log
CLIM X84 1.1
Edition 2
MR-372-J84-62A000$020.mif
Page 6 of 60
62A - 6
AIR CONDITIONING
Fault finding - Introduction62A
V4
Manual air conditioning
and
Climate control
5. FAULT FINDING LOG
You will always be asked for this report:
●when requesting technical assistance from the Techline.
●for approval requests when replacing parts for which approval is obligatory.
●to be enclosed when returning monitored parts on request. The log is needed for warranty reimbursement, and
enables better analysis of the parts removed.
6. SAFETY ADVICE
All work on components requires that the safety rules be obeyed to prevent damage or injury:
–Make sure the battery is properly charged to avoid damaging the computers with a low load.
–Use the appropriate tools.IMPORTANT:
Any fault on a complex system requires thorough fault finding with the appropriate tools. The FAULT
FINDING LOG, which should be completed during the fault finding procedure, ensures a record is kept of
the procedure carried out. It is an essential document when consulting the manufacturer.
IT IS THEREFORE COMPULSORY TO COMPLETE A FAULT FINDING LOG
EVERY TIME A FAULT FINDING PROCEDURE IS PERFORMED.
CLIM X84 1.1
Edition 2
MR-372-J84-62A000$020.mif
Page 23 of 60
62A - 23
AIR CONDITIONING
Fault finding - Conformity check62A
V4
Manual air conditioning
and
Climate control
Subsystem: heating (continued 1)
Computer
(signal generator)Parameter or status
checked or actionDisplay and Notes Fault finding
UCHPR001:Battery voltage.10.5 < X < 14.4 volts.If there is a fault, refer to the
fault finding procedure
for this parameter. If the
fault is still present, carry
out a fault finding test on
the charge circuit.
PR002:Exterior
temperature.X = exterior temperature
± 5 ˚C
(invalid value: 215 ˚C).If there is a fault, refer to the
fault finding procedure
for this parameter.
ET025:Retractable roof.CLOSED or NOT CLOSED
ABSENT if the vehicle does
not have one.If there is a fault, refer to the
fault finding procedure
for this status.
ET091:Engine running:NO
NOTE: This status is
displayed via the UCH but it
is generated by the injection
computer.If there is a fault, refer to the
fault finding procedure
for this status.
(Injection Technical Note).
ET015:Passenger
compartment
blower.INACTIVE
(according to test
conditions: see Notes).If there is a fault, refer to the
fault finding procedure
for this status.
NOTE: This status is only
operative for manual air
conditioning (and heater
versions without air
conditioning).
ET026:Heated rear
screen switch.INACTIVE
(Inhibited with engine
stopped).If there is a fault, refer to the
fault finding procedure
for this status.
ET031:Fast idle request
for RCH.INACTIVE
(Inhibited with engine
stopped).If there is a fault, refer to the
fault finding procedure
for this status.
ET017:Number RCH
required.0, 1, 2 or 3 for Mégane
saloons and sport hatches
(1000 watt RCH).
0, 1, 2, 3, 4 or 5 for Mégane
Scénics (1800 watt RCH).
(according to heat
requirement).If there is a fault, refer to the
fault finding procedure
for this status.
CLIM X84 1.1
Edition 2
MR-372-J84-62A000$060.mif
Page 36 of 60
62A - 36
AIR CONDITIONING
Fault finding - Conformity check62A
V4
Manual air conditioning
and
Climate control
Subsystem: heating (continued 1)
Computer
(signal generator)Parameter or status
checked or actionDisplay and Notes Fault finding
UCHPR001:Battery voltage.12.5 < X < 14.4 volts.If there is a fault, refer to the
fault finding procedure
for this parameter. If the
fault is still present, carry
out fault finding on the
charge circuit.
PR002:Exterior
temperature.X = exterior temperature
± 5˚C
(invalid value: 215 ˚C).If there is a fault, refer to the
fault finding procedure
for this parameter.
ET025:Retractable roof.CLOSED or NOT CLOSED
ABSENT if the vehicle does
not have one.If there is a fault, refer to the
fault finding procedure
for this status.
ET091:Engine running:YES
NOTE: This status is
displayed by the UCH but it
is generated by the injection
computer.If there is a fault, refer to the
fault finding procedure
for this status.
(Injection Technical Note).
ET015:Passenger
compartment
blower.ACTIVE
(according to test
conditions: see Notes).If there is a fault, refer to the
fault finding procedure
for this status.
NOTE: This status is only
operative for manual air
conditioning(and heater
versions without air
conditioning).
ET026:Heated rear
screen switch.ACTIVE if the heated rear
screen is operating.
INACTIVE otherwise.If there is a fault, refer to the
fault finding procedure
for this status.
ET031:Fast idle request
for RCH.ACTIVE if the RCH are
operating.
INACTIVE otherwise.If there is a fault, refer to the
fault finding procedure
for this status.
ET017:Number RCH
required.0, 1, 2 or 3 for Mégane
saloons and sport hatches
(1000 watt RCH).
0, 1, 2, 3, 4 or 5 for Mégane
Scénics (1800 watt RCH).
(according to heat
requirement).If there is a fault, refer to the
fault finding procedure
for this status.
CLIM X84 1.1
Edition 2
MR-372-J84-62A000$060.mif