MITSUBISHI ENDEAVOR 2004 Service Repair Manual
Page 2261 of 3870
STEP 8. Check the wiring harness between front blower relay connector
C-202 (terminal 5) and fusible link (1).
Fig. 190: Identifying Fusible Link
Courtesy of MITSUBISHI MOTOR SALES OF AMERICA.
2004 Mitsubishi Endeavor LS
2004 HVAC Heater Air Conditioning, Ventilation - Endeavor
Page 2262 of 3870
Fig. 191: Locating Connector C
-216
Courtesy of MITSUBISHI MOTOR SALES OF AMERICA.
2004 Mitsubishi Endeavor LS
2004 HVAC Heater Air Conditioning, Ventilation - Endeavor
Page 2263 of 3870
Q: Is the wiring harness between front blower relay connector C-202
(terminal 5) and fusible link (1) in good condition?
YES:
The front blower motor should operate normally.
NO:
Repair the wiring harness. The front blower motor should operate
normally.
STEP 9. Check the wiring harness between A/C-ECU connector C-16
(terminal 9) and front blower relay connector C-202 (terminal 3).
NOTE: Also check junction block connector C-216 for loose,
corroded, or damaged terminals, or terminals pushed
back in the connector. If junction block connector C-216
is damaged, repair or replace the connector as
described in HARNESS CONNECTOR INSPECTION
.
2004 Mitsubishi Endeavor LS
2004 HVAC Heater Air Conditioning, Ventilation - Endeavor
Page 2264 of 3870
Fig. 192: Locating Connector C
-16
Courtesy of MITSUBISHI MOTOR SALES OF AMERICA.
2004 Mitsubishi Endeavor LS
2004 HVAC Heater Air Conditioning, Ventilation - Endeavor
Page 2265 of 3870
2004 Mitsubishi Endeavor LS
2004 HVAC Heater Air Conditioning, Ventilation - Endeavor
Page 2266 of 3870
Fig. 193: Locating Connector C
-211
Courtesy of MITSUBISHI MOTOR SALES OF AMERICA.
Q: Is the wiring harness between A/C-ECU connector C-16 (terminal 9)
and front blower relay connector C-202 (terminal 3) in good condition?
YES:
Go to Step 10.
NO:
Repair the wiring harness. The front blower motor should operate
normally.
STEP 10. Check the wirin
g harness between front blower motor connector
C-111 (terminal 1) and front blower relay connector C-202 (terminal 4). NOTE: Also check junction block connector C-211 for loose,
corroded, or damaged terminals, or terminals pushed
back in the connector. If junction block connector C-211
is damaged, repair or replace the connector as
described in HARNESS CONNECTOR INSPECTION
.
2004 Mitsubishi Endeavor LS
2004 HVAC Heater Air Conditioning, Ventilation - Endeavor
Page 2267 of 3870
Fig. 194: Locating Connector C
-111
Courtesy of MITSUBISHI MOTOR SALES OF AMERICA.
2004 Mitsubishi Endeavor LS
2004 HVAC Heater Air Conditioning, Ventilation - Endeavor
Page 2268 of 3870
Fig. 195: Locating Connectors C
-202 And C
-215
Courtesy of MITSUBISHI MOTOR SALES OF AMERICA.
2004 Mitsubishi Endeavor LS
2004 HVAC Heater Air Conditioning, Ventilation - Endeavor
Page 2269 of 3870
Q: Is the wiring harness between front blower motor connector C-111
(terminal 1) and front blower relay connector C-202 (terminal 4) in good
condition?
YES:
The front blower motor should operate normally.
NO:
Repair the wiring harness. The front blower motor should operate
normally.
STEP 11. Check the front blower fan and motor operation.
When battery voltage is applied between the terminals, check that the motor
operates. Also, check that there is no abnormal noise.
Q: Is there any abnormal noise?
YES:
Go to Step 12.
NO:
Replace the front blower relay. The front blower motor should
o
perate normall
y.
NOTE: Also check junction block connector C-215 for loose,
corroded, or damaged terminals, or terminals pushed
back in the connector. If junction block connector C-215
is damaged, repair or replace the connector as
described in HARNESS CONNECTOR INSPECTION
.
2004 Mitsubishi Endeavor LS
2004 HVAC Heater Air Conditioning, Ventilation - Endeavor
Page 2270 of 3870
Fig. 196: Checking Front Blower Fan And Motor Operation
Courtesy of MITSUBISHI MOTOR SALES OF AMERICA.
STEP 12. Check power transistor connector C-108 for loose, corroded or
damaged terminals, or terminals pushed back in the connector.
Q: Is power transistor connector C-108 in good condition?
YES:
Go to Step 13.
NO:
Repair or replace the connector. Refer to
HARNESS
CONNECTOR INSPECTION
. The front blower motor should operate
normall
y.
2004 Mitsubishi Endeavor LS
2004 HVAC Heater Air Conditioning, Ventilation - Endeavor