AIR CONDITIONING
62
62 - 2
AIR COND
ITIONING UNIT
DISMOUNTING
Make the unit functioning for at least 10 minutes (if the unit permits).
Drain the circuit at the filling equipment.
Measure the quantity of recovered refrigerated fluid.
Release the access to the component that is needed to be changed.
Disconnect the connections.
In order to avoid the moisture infiltration, protect with protection covers.
Dismount the component.
REMOUNTING
P ut special c ompressor oil on the new elements thread and on the gaskets.
AT TENT ION
The new components must be obligatory provided with protection c overs.
Remove t he protection covers, connect the new component on t he free connection,
and tighten it by hand.
Place the component correctly.
Tighten it at couple.
Refill with refrigerant fluid and oil.
The filling up with oil for different repairs is to be performed as follows: add in the charging
equipment container, the recovered oil quantity, plus an oil quantity, as it follows:
- sudden damaged of one of the unit’s element or leakage 100ml
- condenser replacement 30 ml
- evaporator replacement 30 ml
- dryer filter replacement 15 ml
- pipe replacement 10 ml
For compressor dismounting/remounting without replacement add 120 ml.
If there are signs of moisture in the air conditioning circuit, replace the dryer filter tank.
62
GENERALITIES
!
vnx.su
Page 416 of 933

AIR CONDITIONING
62
62 - 9
PRESSURE CONTROLLER
(low pressure, high pressure, medium pressure, in accordance
with the specification) or pressure capture
- low pressure – disconnect when the pressure in the low pressure circuit is lower than
1,96 +/-0,2 bar , reestablishing at a higher pressure than 2,16 +/- 0,2 bar; - higher pressure – disconnect when the pressure in the high pressure circuit is higher than
31,4 +/-2 bar , reestablishing at a higher pre ssure than 25,5 +/-2 bar; - medium pre ssure - start s the bl ower on t he second level speed, when t he pressure i s
higher than 17,7+/-1bar and stops the blower at a lower pressure 13,7+/- 1,2.
Thermostatic expansion valve allows the reduction of the refrigerant liquid pressure which is
coming from t he condenser, passing through the tank filter and i s continuously adjusting the
refrigerant flow from the evaporator, to reach the compressor in vapor condition. PRESSURE CONTROLLER
The good operation of the air conditioning unit is ensured by a dryer filter tank that ha s the
purpose to protect the unit. The filter’s purpose is to absorb the eventually solid particles found
in the oil and refrigerant liquid circulation.
The interception is needed as they might block the operation of the thermostatic expansion
valve or may produce the compressor mobile parts worn or gripping.
DETECTION OF REFRIGERANT F LUID LEAKAGE
In order to detect the refrigerant liquid leakage, it is used a detector, calibrated to detect
leakage of 9gr. /year.