ad blue RENAULT KANGOO 1998 KC / 1.G Heating And Ventilation Workshop Manual
[x] Cancel search | Manufacturer: RENAULT, Model Year: 1998, Model line: KANGOO, Model: RENAULT KANGOO 1998 KC / 1.GPages: 73
Page 5 of 73
Fit the complete control panel without screwing it
in place.
On the bottom right-hand side
Fit the cable on to the mark.
Place the air distribution control on position
, place the heater control on the maxi-
mum cold position (blue mark) and check that the
flaps are at their end stop.
HEATING
Control cables
61
98815R92224R1
REMOVAL
The control cables can be removed without remo-
ving the dashboard.
Remove :
- the ashtray,
- the control unit.
In the bottom right-hand side of the passenger
compartment
Remove the securing clip (E) (depending on which
cable is to be replaced) :
- from the hot/cold air flap control cable,
or
- from the air distribution cable.
REFITTING
Route the cable through the control panel loca-
tion.
Push back the flap control to prevent the cable
from coming out of its location.
Fit securing clips (E) and (M).
61-2
Page 18 of 73
c11010.0
AIR CONDITIONING
Fault finding - Interpretation of XR25 bargraphs62
KANGOO
ALL TYPES
You may begin the fault finding procedure.AFTER
REPAIR
Right-hand bargraph 1 extinguished
XR25 / CONTROL UNIT COMMUNICATION
1
None.NOTES
Fiche n° 61
Before establishing communication between the XR25 and the control unit, check that you have switched
on the ignition.
Ensure that the XR25 is not the cause of the fault by trying to communicate with a computer on another
vehicle.
Check that the ISO interface is in position S8 and that you are using the latest version of the XR25 cassette
and the correct access code (D 17).
Check the battery voltage (U > 10.5 volts). Recharge the battery if necessary.
Check that the control unit connectors are engaged correctly.
Check that the air conditioning control unit is supplied correctly:
- earth on track 4 of the red 15-way connector
-+ after ignition on track 1 of the blue 30-way connector
-+ after ignition on track 6 of the red 15-way connector
-+ fuse board on track 5 of the red 15-way connector
Check that the diagnostic socket is supplied correctly:
track K track 6of the air conditioning control unit
track L track 3blue 30-way connector
If there is still no dialogue between the XR25 and the control unit, change the air conditioning control
unit.
62-7
Page 24 of 73
Check the continuity and insulation from earth and from 12 volts of the electrical wiring between tracks:
air recirculation B2 27air conditioning control unit
motor connector B3 26 blue 30-way connector
Repair the faulty electrical wiring.
Check the condition of the electrical wiring between tracks:
control A2 3air conditioning control unit
panel red 15-way connector
Repair if necessary.
c11010.0
AIR CONDITIONING
Fault finding - Interpretation of XR25 bargraphs62
KANGOO
ALL TYPES
Enter G0** on the XR25.
Check that the system operates correctly.AFTER
REPAIR
Right-hand bargraph 4 illuminated
AIR RECIRCULATION MOTOR
4
This fault only appears on the XR25 if air recirculation is selected.NOTES
Fiche n° 61
Check the condition of the air recirculation flap control motor.
On the motor connector, measure the resistance between the two tracks.
Change the recirculation motor if necessary.
If the fault persists, change the air conditioning control unit.
62-13
Page 43 of 73
Check the insulation and continuity of the
electrical wiring between:
computer 26 B3 resistance
blue 30-way unit
connector 27 B2 connector
Is the wiring in good condition?
yes
Check the condition of the electrical wiring
between:
control computer
panel A2 3 15-way
connector
Is the wiring in good condition?
yes
c11010.0
AIR CONDITIONING
Fault finding charts
62
KANGOO
ALL TYPES
AFTER
REPAIR
CHART 11RECIRCULATION FLAP DOES NOT OPERATE
NOTES
noRepair the faulty wiring.
noChange the control panel.
noRepair the faulty
electrical wiring.
yes
A
Before carrying out any work, check that the customer uses the air conditioning
correctly.
Non regulated air conditioning.
First of all check the condition of fuses
+battery, + fuse board, +after ignition.
Change them if necessary.
With the ignition on and air recirculation
selected, check that 12 V is present on track
A2 of the control panel.
Is 12 V present?
Check that the components which were removed are connected correctly.
Check that the system operates correctly.
62-32