ECU RENAULT TWINGO 2009 2.G Heating And Air Conditioning - Climate Control Workshop Manual
[x] Cancel search | Manufacturer: RENAULT, Model Year: 2009, Model line: TWINGO, Model: RENAULT TWINGO 2009 2.GPages: 99
Page 3 of 99

62B-3
MR-413-X44-62B000$046_eng.mif
V1
CLIMATE CONTROL
Fault finding - Introduction
                            
Vdiag No.: 44
62B
Faults
Faults are declared as either present or stored (depending on whether they appeared in a certain context and have 
disappeared since, or whether they remain present but have not been diagnosed within the current context).
The present or stored status of faults should be taken into consideration when the diagnostic tool is switched on 
after the + after ignition feed (without any system components being active).
For a present fault, apply the procedure described in the Interpretation of faults section.
For a stored fault, note the faults displayed and apply the Notes section.
If the fault is confirmed when the instructions in the Notes section are applied, the fault is present. Deal with the 
fault.
If the fault is not confirmed, check:
–the electrical lines which correspond to the fault,
–the connectors on these lines (corrosion, bent pins, etc.),
–the resistance of the component detected as faulty,
–the condition of the wires (melted or split insulation, wear).
Conformity check
The aim of the conformity check is to check data that does not produce a fault on the diagnostic tool because the 
data is inconsistent. Therefore, this stage is used to: 
–carry out fault finding on faults that do not have a fault display, and which may correspond to a customer 
complaint.
–check that the system is operating correctly and that there is no risk of a fault recurring after repairs.
This section gives the fault finding procedures for statuses and parameters and the conditions for checking them.
If a status is not behaving normally or a parameter is outside the permitted tolerance values, consult the 
corresponding fault finding page.
Special notes on the conformity check for the air conditioning function:
All variables (statuses and parameters) and commands required for the air conditioning function are divided into 
three sub-functions:
●The COLD LOOP sub-function groups together all the information required for producing cold air.
●The HEATING sub-function groups together all the information required for producing warm air.
●The PASSENGER COMPARTMENT VENTILATION sub-function groups together all the information relating to 
ventilation and the mixing and distribution of air within the passenger compartment. 
Page 25 of 99

62B-25
MR-413-X44-62B000$414_eng.mif
V1
62B
CLIMATE CONTROL
Fault finding - Interpretation of faults
DF001
PRESENT
OR
STOREDCOMPUTER
1. DEF:   Internal electronic fault
NOTESConditions for running fault finding on a present or stored fault:
Apply this fault finding procedure if the fault reappears as present or stored after the 
ignition is switched of f and on again.
Switch off the ignition and wait for the immobiliser warning light (Power-latch) to come one,
–Switch on the ignition again.
–Start the engine and switch on the air conditioning.
If the fault recurs, contact the Techline.
If the fault does not reappear: leave the climate control switched on and select various ventilation and air 
distribution settings to check that the system is operating correctly.
–Check that no fault is displayed.
If the fault is still present, contact the Techline.
AFTER REPAIRFollow the instructions to confirm repair.
If the computer was replaced (at the request of the Techline), reconfigure the 
computer (see Configurations and programming).
Deal with any other faults.
CLIM_V44_DF001
                  
Vdiag No.: 44
MR-413-X44-62B000$414_eng.mif 
Page 30 of 99

62B-30
MR-413-X44-62B000$414_eng.mif
V1
CLIMATE CONTROL
Fault finding - Interpretation of faults
                            
Vdiag No.: 44
62B
DF012
CONTINUED
With the connector disconnected, measure the resistance value of component 1115 between the following 
connections:
●connections S and 38KY,
●connections S and 38LA,
●connections S and 38LB,
●connections S and 38KZ.
If the connection or connections are faulty (see Technical Note 6015A, Repairing electrical wiring, Wiring: 
Precautions for repair), repair the wiring, otherwise replace it.
The results of the four checks should be 100 ΩΩ Ω Ω
 ± 5      
ΩΩ Ω Ω
     
at 20 ˚C, replace the distribution motor if this is not the case.
If the fault is still present, remove the distribution motor but leave it electrically connected, send a motor command 
from the distribution buttons on the control panel: switch the distribution setting to demisting (a value of 100 %), 
then switch the distribution setting to air vent (a value of 0 %), the motor must change from one direction to the 
other. If the connections tested earlier match but the motor does not switch during the commands, replace the 
distribution motor.
If the commands have been executed correctly, check that the distribution motor flap is not blocked by trying to 
move the gears. Repair if necessary.
If the fault is still present, contact the Techline.
AFTER REPAIRClear the stored faults.
Follow the instructions to confirm repair.
If the motor has been replaced (see Configuration and programming).
Deal with any other faults. 
Page 71 of 99

62B-71
MR-413-X44-62B000$828_eng.mif
V1
                            
Vdiag No.: 44CLIMATE CONTROL
Diagnostic - Fault finding chart62B
ALP 2
CONTINUED 1
With the distribution motor removed, manually 
activate the distribution flaps by turning the centre of 
the control fully from one side to the other.
Does the flap cover the whole range of 
movement, without any areas of resistance?
YES
Remove the footwell vent ducts (lower ducts) to 
check that the lower flap control linkages are 
present and correctly fitted (they are connected to 
the upper flaps).
Also ensure that lower flaps move when the 
distribution flap manual control is operated.
Do the footwell (lower) distribution flaps move 
when the distribution flaps are controlled?
YES
NORemove the dashboard in order to check 
that there is nothing preventing the flaps 
from moving (see MR 412, Bodywork, 
57A, Interior accessories, Dashboard: 
Removal - Refitting). Carry out any 
repairs (eliminate any foreign bodies 
which may be blocking the flaps and 
lubricate the centre of the flap control).
Replace the distribution - ventilation unit if 
it is not possible to repair it.
NOIf the mountings of the lower flap control 
linkages are not damaged: resecure the 
linkages and grease them slightly. If a 
repair is not possible or if the mountings 
are damaged: replace the distribution - 
ventilation unit.
AFTER REPAIRCarry out a complete check with the diagnostic tool.