ESP RENAULT TWINGO 2009 2.G Heating And Air Conditioning - Climate Control Workshop Manual
[x] Cancel search | Manufacturer: RENAULT, Model Year: 2009, Model line: TWINGO, Model: RENAULT TWINGO 2009 2.GPages: 99
Page 3 of 99

62B-3
MR-413-X44-62B000$046_eng.mif
V1
CLIMATE CONTROL
Fault finding - Introduction
                            
Vdiag No.: 44
62B
Faults
Faults are declared as either present or stored (depending on whether they appeared in a certain context and have 
disappeared since, or whether they remain present but have not been diagnosed within the current context).
The present or stored status of faults should be taken into consideration when the diagnostic tool is switched on 
after the + after ignition feed (without any system components being active).
For a present fault, apply the procedure described in the Interpretation of faults section.
For a stored fault, note the faults displayed and apply the Notes section.
If the fault is confirmed when the instructions in the Notes section are applied, the fault is present. Deal with the 
fault.
If the fault is not confirmed, check:
–the electrical lines which correspond to the fault,
–the connectors on these lines (corrosion, bent pins, etc.),
–the resistance of the component detected as faulty,
–the condition of the wires (melted or split insulation, wear).
Conformity check
The aim of the conformity check is to check data that does not produce a fault on the diagnostic tool because the 
data is inconsistent. Therefore, this stage is used to: 
–carry out fault finding on faults that do not have a fault display, and which may correspond to a customer 
complaint.
–check that the system is operating correctly and that there is no risk of a fault recurring after repairs.
This section gives the fault finding procedures for statuses and parameters and the conditions for checking them.
If a status is not behaving normally or a parameter is outside the permitted tolerance values, consult the 
corresponding fault finding page.
Special notes on the conformity check for the air conditioning function:
All variables (statuses and parameters) and commands required for the air conditioning function are divided into 
three sub-functions:
●The COLD LOOP sub-function groups together all the information required for producing cold air.
●The HEATING sub-function groups together all the information required for producing warm air.
●The PASSENGER COMPARTMENT VENTILATION sub-function groups together all the information relating to 
ventilation and the mixing and distribution of air within the passenger compartment. 
Page 6 of 99

62B-6
MR-413-X44-62B000$046_eng.mif
V1
CLIMATE CONTROL
Fault finding - Introduction
                            
Vdiag No.: 44
62B
4. FAULT FINDING PROCEDURE (CONTINUED)
Wiring check
Fault finding problems
Disconnecting the connectors and/or manipulating the wiring harness may temporarily remove the cause of a fault.
Electrical measurements of voltage, resistance and insulation are generally correct, especially if the fault is not 
present when the analysis is made (stored fault).
Visual inspection of the connection:
●Check that the connector is connected correctly and that the male and female parts of the connection are 
correctly coupled.
Visual inspection of the area around the connection:
●Check the condition of the mounting (pin, strap, adhesive tape, etc.) if the connectors are attached to the 
vehicle.
●Check that there is no damage to the wiring trim (sheath, foam, adhesive tape, etc.) near the wiring.
●Check that there is no damage to the electrical wires at the connector outlets, in particular on the 
insulating material (wear, cuts, burns, etc.).
Disconnect the connector to continue the checks.
Visual inspection of the plastic casing:
●Check that there is no mechanical damage (casing crushed, cracked, broken, etc.), in particular to the 
fragile components (lever, lock, openings, etc.).
●Check that there is no heat damage (casing melted, darker, deformed, etc.).
●Check that there are no stains (grease, mud, liquid, etc.).
Visual inspection of the metal contacts:
(The female contact is called CLIP. The male contact is called TAB.)
●Check that there are no bent contacts (the contact is not inserted correctly and can come out of the back 
of the connector). The spring contact of the connector when the wire is gently pulled.
●Check that there is no damage (folded tabs, clips open too wide, blackened or melted contact, etc.).
●Check that there is no oxidation on the metal contacts.  Note:
Carry out each requested check visually. Do not remove a connector if it is not required.
Note:
Repeated connections and disconnections alter the functionality of the connectors and increase the risk of poor 
electrical contact. Limit the number of connections/disconnections as much as possible.
Note:
The check is carried out on the 2 parts of the connection. There may be two types of connections:
–Connector / Connector
–Connector / Device 
Page 21 of 99

62B-21
MR-413-X44-62B000$276_eng.mif
V1
62B
CLIMATE CONTROL
Fault finding - Replacement of components
REPLACING THE CLIMATE CONTROL COMPUTER
–Note the computer configuration according to the optional equipment fitted on the vehicle (see climate control 
computer configuration) or using the Shared World Information (ICM).
–Ensure that the ignition is switched off.
–After approval from the Techline, replace the computer.
–Switch on the ignition and carry out a check using the diagnostic tool.
–Configure the computer according to the vehicle specifications.
–Switch off the ignition and then back on for the configurations to register.
–Check in the Read configuration menu that the configurations have been recognised correctly.
–Check for faults and apply the corresponding fault finding procedure for any faults shown on the diagnostic tool.
–Clear any stored faults.
–Run command VP001 Enter VIN.
–Start the engine, switch on the air conditioning and ensure that it is operating correctly. WARNING
Before replacing the climate control computer, check that it is faulty (read faults, conformity of variables, 
read customer complaints). Replacement of the computer must be authorised by the Techline after a fault 
finding log has been completed and submitted.
                  
Vdiag No.: 44
MR-413-X44-62B000$276_eng.mif 
Page 22 of 99

62B-22
MR-413-X44-62B000$322_eng.mif
V1
62B
CLIMATE CONTROL
Fault finding - Configuration and programming
CLIMATE CONTROL COMPUTER CONFIGURATION
The climate control computer has three configuration functions. These configurations need to be set after replacing 
the computer.
These three configurations are important as they ensure that climate control is optimised within the vehicle (better 
control compared to automatic air conditioning). If these configurations are not entered correctly, cold air and warm 
air production will be severely affected.
These configurations can be accessed in repair mode by the diagnostic tool and can only be entered using 
the fault finding by computer menu as opposed to the fault finding by function menu.
These configurations can also be read using the diagnostic tool in repair mode to ensure they have been correctly 
set. Configurations can be read in fault finding by computer mode and fault finding by function mode.
Configuration Option Configuration reading
CF044Vehicle type – New TwingoLC013Vehicle type
CF024Geographical zone– Zone 1
– Zone 2LC046Geographical zone
CF117Type of heating 
resistors – None
– 900 WLC044Type of heating 
resistors 
WARNING
–The "ZONE 1" configuration must be selected for HOT AND HUMID COUNTRIES which correspond to the 
technical and legislative criteria available on the Shared World Information.
–The "ZONE 2" configuration must be selected for TEMPERATE COUNTRIES which correspond to the 
technical and legislative criteria available on the Shared World Information.
Note:
In hot and humid climates, when the heating and air conditioning system is in operation, condensation 
may form on the outside of the windscreen.
The "ZONE 1" configuration corrects this customer complaint.
Note:
In fault finding by function mode, the diagnostic tool can also display the configuration readings of the other 
computers involved in the air conditioning function. All of the air conditioning function configurations (of the 
injection computer and UCH computer) are listed (See 62C, Air conditioning).
                  
Vdiag No.: 44
MR-413-X44-62B000$322_eng.mif 
Page 24 of 99

62B-24
MR-413-X44-62B000$368_eng.mif
V1
62B
CLIMATE CONTROL
Fault finding - Fault summary table
SUMMARY OF SENSORS AND ACTUATORS ON WHICH FAULT FINDING CAN BE PERFORMED BY THE 
CLIMATE CONTROL COMPUTER (with corresponding design office codes)
Tool faultAssociated 
DTCDiagnostic tool title
DF0019105 Computer
DF0079101 Interior temperature sensor circuit
DF0109107 Mixing motor circuit
DF0129108 Distribution motor circuit
DF0219106 Air recirculation motor circuit
                  
Vdiag No.: 44
MR-413-X44-62B000$368_eng.mif 
Page 32 of 99

62B-32
MR-413-X44-62B000$460_eng.mif
V1
62B
CLIMATE CONTROL
Fault finding - Conformity check
SUB-FUNCTION: PASSENGER COMPARTMENT VENTILATION
NOTESOnly carry out this conformity check after a complete check with the diagnostic tool 
(fault reading and configuration checks).
Application conditions: engine stopped with ignition on (12 V APC), AIR 
CONDITIONING OFF (air conditioning compressor not activated).
Note:
–Read the parameters when the vehicle is cold (in the morning) to check the 
conformity of the temperature parameters (without thermometer). The two 
temperatures should be practically the same (as should the coolant temperature 
given by the injection system).
–The invalid values given in this check correspond to the value sent by the diagnostic 
tool (substitute value) when the sensor in question is faulty. A sensor fault can be 
detected when these invalid values are displayed (this is an important point for 
sensors on which fault finding cannot be performed, e.g. exterior temperature 
sensor).
Delayed illumination of the exterior temperature sensor LCD indicates that an invalid 
value has been received concerning the exterior temperature sensor.
FunctionParameter or Status 
checked or ActionDisplay and Notes Fault finding
Passenger 
compartment 
blowerET141:Passenger 
compartment 
blowerRUNNING 
or 
 STOPPED 
After a user requestIn the event of a fault, refer to the 
interpretation of this status.
PR019:Passenger 
compartment 
fan PWM settingSpeed 0 = 0 %
Speed 8 = 100 %
Note:
The PWM signal is a 
modulated control 
voltage used to control 
the air conditioning 
blower power module.If there is a fault or for more 
information (to find the 
intermediate speed 
percentages), refer to the 
interpretation of this 
parameter.
Note:
If the parameter varies correctly, 
but the passenger compartment 
blower unit does not operate: 
consult ALP 5 "Air flow fault"
Air flapsPR012:Mixing flap 
positionFrom 0 % (“Maximum 
cold” position: 15 ˚C)
to 100 % (“Maximum 
hot” position: 27 ˚C).In the event of a fault, see the 
interpretation of this 
parameter.
ET062:Recirculation 
flap positionOPEN if the flap is in the 
external air position.
CLOSED if the flap is in 
the recirculation 
position.In the event of a fault, refer to the 
interpretation of this status.
PR011:Distribution flap 
positionFrom 0 % (Air vent 
position)
to 100 % (De-icing 
position)In the event of a fault, see the 
interpretation of this 
parameter.
CLIM_V44_CCONF
                  
Vdiag No.: 44
MR-413-X44-62B000$460_eng.mif 
Page 33 of 99

62B-33
MR-413-X44-62B000$460_eng.mif
V1
                            
Vdiag No.: 44CLIMATE CONTROL
Fault finding - Conformity check62B
SUB-FUNCTION: PASSENGER COMPARTMENT VENTILATION (CONTINUED)
NOTESOnly carry out this conformity check after a complete check with the diagnostic tool 
(fault reading and configuration checks).
Application conditions: engine stopped with ignition on (12 V APC), CLIMATE 
CONTROL  OFF (air conditioning compressor not engaged).
FunctionParameter or Status 
checked or ActionDisplay and Notes Fault finding
TemperaturesPR001: Interior 
temperatureX = interior 
temperature ± 5 ˚C 
(invalid value: 87.5 ˚C)In the event of a fault, see the 
interpretation of this parameter.
PR002: External 
temperatureX = exterior 
temperature ± 5 ˚C 
(invalid value: 215 ˚C)In the event of a fault, see the 
interpretation of this parameter
Note: 
This parameter is displayed via the 
climate control computer but is 
generated by the UCH.
Motor activationAC001:Passenger 
compartment 
blowerWhen this command is 
run the passenger 
compartment blower 
comes on.In the event of a fault, refer to the 
interpretation of this command.
AC002:Recirculation 
motor: exterior airThis command is used to 
actuate the air 
recirculation motor to 
check that it is working.In the event of a fault, refer to the 
interpretation of this command.
AC003:Recirculation 
motor: 
recirculationThis command is used to 
actuate the air 
recirculation motor to 
check that it is working.In the event of a fault, refer to the 
interpretation of this command.
AC007:Distribution 
motor: de-icingThis command is used to 
activate the ventilation/
de-icing distribution flap 
to check that it is working.In the event of a fault, refer to the 
interpretation of this command.
AC006:Distribution 
motor: air ventThis command is used to 
activate the ventilation/
de-icing distribution flap 
to check that it is working.In the event of a fault, refer to the 
interpretation of this command.
AC004:Mixer motor: 
maximum coldThis command is used to 
activate the mixing flap to 
check that it is working.In the event of a fault, refer to the 
interpretation of this command.
AC005:Mixer motor: 
maximum hotIn the event of a fault, refer to the 
interpretation of this command. 
Page 34 of 99

62B-34
MR-413-X44-62B000$460_eng.mif
V1
                            
Vdiag No.: 44CLIMATE CONTROL
Fault finding - Conformity check62B
COLD LOOP SUB-FUNCTION
NOTESOnly carry out this conformity check after a complete check with the diagnostic tool 
(fault reading and configuration checks).
Application conditions: engine stopped with ignition on (12 V APC), CLIMATE 
CONTROL  OFF (air conditioning compressor not engaged).
FunctionParameter or Status 
checked or ActionDisplay and Notes Fault finding
Request to engage 
the compressorET140:Air conditioning 
requestINACTIVEIn the event of a fault, refer to the 
interpretation of this status.
Passenger 
compartment 
blowerET141:Passenger 
compartment 
blowerRUNNING 
or 
STOPPED 
After a user requestIn the event of a fault, refer to the 
interpretation of this status.
CompressorET020:Compressor 
controlINACTIVEIn the event of a fault, refer to the 
interpretation of this status.
TemperaturesPR001:Interior 
temperatureX = interior 
temperature ± 5 ˚C
(invalid value: 87.5 ˚C)In the event of a fault, see the 
interpretation of this 
parameter.
PR002:External 
temperatureX = exterior 
temperature ± 5 ˚C
(invalid value: 215 ˚C)In the event of a fault, see the 
interpretation of this 
parameter
Note: 
This parameter is displayed via 
the climate control computer but 
is generated by the UCH.
Air flapsPR012:Mixing flap 
positionFrom 0 % (“Maximum 
cold” position: 15 ˚C)
to 100 % (“Maximum 
hot” position: 27 ˚C).In the event of a fault, see the 
interpretation of this 
parameter. 
Page 36 of 99

62B-36
MR-413-X44-62B000$460_eng.mif
V1
                            
Vdiag No.: 44CLIMATE CONTROL
Fault finding - Conformity check62B
MAIN SCREEN
NOTESOnly carry out this conformity check after a full check using the diagnostic tool 
(fault reading and configuration checks).
Application conditions: engine stopped with ignition on (12 V APC), AIR 
CONDITIONING OFF (air conditioning compressor not activated).
Note:
This page lists the statuses and parameters provided by the climate control computer 
but which are not associated with the three sub-functions given in the conformity 
check (PASSENGER COMPARTMENT VENTILATION, COLD LOOP and HEATING 
sub-functions).
FunctionParameter or Status 
checked or ActionDisplay and Notes Fault finding
Electrical suppliesPR092:Battery voltage10.5 V < X <14.4 VIn the event of a fault, see the 
interpretation of this 
parameter.
ET083:+ 12 V after 
ignition present ABSENT: Ignition off. 
PRESENT: Ignition on.In the event of a fault, refer to the 
interpretation of this status.
ET002:+ 12 V side 
lightsABSENT: Side lights off. 
PRESENT: Side lights 
on.In the event of a fault, refer to the 
interpretation of this status.
PR122:Night lighting 
level15 % = minimum 
lighting level
99 % = maximum 
lighting level
(side lights 
off: 102 %)In the event of a fault, refer to the 
interpretation of this status.
Note: 
This parameter is displayed via 
the climate control computer but 
is generated by the instrument 
panel. 
Page 37 of 99

62B-37
MR-413-X44-62B000$460_eng.mif
V1
                            
Vdiag No.: 44CLIMATE CONTROL
Fault finding - Conformity check62B
SUB-FUNCTION: PASSENGER COMPARTMENT VENTILATION
NOTESOnly carry out this conformity check after a full check using the diagnostic tool 
(fault reading and configuration checks).
Application conditions: engine running, AIR CONDITIONING ON (air conditioning 
compressor activated).
Note:
–Read the parameters when the vehicle is cold (in the morning) to check the 
conformity of the temperature parameters (without thermometer). The two 
temperatures should be practically the same (as should the coolant temperature 
given by the injection system).
–The invalid values given in this check correspond to the value sent by the diagnostic 
tool (substitute value) when the sensor in question is faulty. A sensor fault can be 
detected when these invalid values are displayed (this is an important point for 
sensors on which fault finding cannot be performed, e.g. exterior temperature 
sensor).
FunctionParameter or Status 
checked or ActionDisplay and Notes Fault finding
Passenger 
compartment 
blowerPR019: Passenger 
compartment 
fan PWM settingSpeed 0 = 0 %
Speed 8 = 100 %
Note:
The PWM signal is a 
modulated control 
voltage used to control 
the air conditioning 
blower power module.If there is a fault or for more 
information (to find the 
intermediate speed 
percentages), refer to the 
interpretation of this 
parameter.
Note:
If the parameter varies correctly, 
but the passenger compartment 
blower unit is not working: refer to 
fault finding chart no. 5.
ET141: Passenger 
compartment 
blowerRUNNING 
or 
STOPPED 
After a user request.In the event of a fault, refer to the 
interpretation of this status.
Air flapsPR012: Mixing flap 
positionFrom 0 % (“Maximum 
cold” position: 15 ˚C)
to 100 % (“Maximum 
hot” position: 27 ˚C).In the event of a fault, see the 
interpretation of this 
parameter.
ET062: Recirculation 
flap positionOPEN if the flap is in the 
external air position. 
CLOSED if the flap is in 
the recirculation 
position.In the event of a fault, refer to the 
interpretation of this status.
PR011: Distribution flap 
positionFrom 0 % (Air vent 
position)
to 100 % (De-icing 
position).In the event of a fault, refer to the 
interpretation of this status.