Compressor SUZUKI SWIFT 2005 2.G Service Service Manual
[x] Cancel search | Manufacturer: SUZUKI, Model Year: 2005, Model line: SWIFT, Model: SUZUKI SWIFT 2005 2.GPages: 1496, PDF Size: 34.44 MB
Page 956 of 1496

Downloaded from www.Manualslib.com manuals search engine 7B-8 Air Conditioning System: Manual Type
Cool air does not come 
out or insufficient cooling 
(A/C system normal 
operation)Insufficient or excessive charge of 
refrigerant
Check the amount of refrigerant and system 
for leaks.
Condenser clogged Check condenser referring to “Condenser 
Assembly On-Vehicle Inspection”.
A/C evaporator clogged or frosted Check A/C evaporator and evaporator 
thermistor (evaporator temperature sensor) 
referring to “Evaporator Inspection” and 
“Evaporator Thermistor (Evaporator 
Temperature Sensor) Inspection”.
Evaporator thermistor (Evaporator 
temperature sensor) faulty Check evaporator thermistor (Evaporator 
temperature sensor) referring to “Evaporator 
Thermistor (Evaporator Temperature Sensor) 
Inspection”.
Expansion valve faulty Check expansion valve referring to “Expansion 
Valve Inspection”.
Desiccant clogged Replace receiver/dryer.
Compressor drive belt loosened or 
broken Adjust or replace drive belt.
Magnet clutch faulty Check magnet clutch referring to “Magnet 
Clutch Inspection”.
Compressor faulty Check compressor.
Air in A/C system Replace receiver/dryer, and then perform 
evacuation and charge referring to “Operation 
Procedure for Refrigerant Charge”.
Air leaking from HVAC unit or air duct Repair as necessary.
Heater and ventilation system faulty Check HVAC unit.
Blower motor faulty Check blower motor referring to “Blower Motor 
Inspection in Section 7A”.
Excessive compressor oil in A/C system Drain excessive compressor oil from A/C 
system circuit and compressor.
Cool air does not come 
out only intermittently Wiring connection faulty
Repair as necessary.
Expansion valve faulty Check expansion valve referring to “Expansion 
Valve Inspection”.
Excessive moisture in A/C system Replace receiver/dryer, and then perform 
evacuation and charge referring to “Operation 
Procedure for Refrigerant Charge”.
Magnet clutch faulty Check magnet clutch referring to “Magnet 
Clutch Inspection”.
Excessive amount of refrigerant Check the amount of refrigerant.
Cool air comes out only 
when driving vehicle at 
high speed Condenser clogged
Check condenser referring to “Condenser 
Assembly On-Vehicle Inspection”.
Insufficient charge of refrigerant Check the amount of refrigerant and system 
for leaks.
Air in A/C system Replace receiver/dryer, and then perform 
evacuation and charge referring to “Operation 
Procedure for Refrigerant Charge”.
Compressor drive belt loosened or 
broken Adjust or replace drive belt.
Compressor faulty Check compressor.
Cool air does not come 
out only when driving 
vehicle at high speed Excessive amount of refrigerant
Check the amount of refrigerant.
A/C evaporator frosted Check A/C evaporator and evaporator 
thermistor (evaporator temperature sensor) 
referring to “Evaporator Inspection” and 
“Evaporator Thermistor (Evaporator 
Temperature Sensor) Inspection”.
Condition Possible cause Correction / Reference Item  
Page 957 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-9
Abnormal Noise Symptom Diagnosis of A/C SystemS7RS0B7214002
Abnormal Noise from Compressor
Abnormal Noise from Magnetic Clutch
Abnormal Noise from Tubing
Abnormal Noise from Condenser Assembly
Abnormal Noise from Crankshaft PulleyInsufficient airflow of 
cooled air
A/C evaporator clogged or frosted
Check A/C evaporator and evaporator 
thermistor (evaporator temperature sensor) 
referring to “Evaporator Inspection” and 
“Evaporator Thermistor (Evaporator 
Temperature Sensor) Inspection”.
Air leaking from HVAC unit or air duct Repair as necessary.
Blower motor faulty Check blower motor referring to “Blower Motor 
Inspection in Section 7A”.
Wiring or grounding faulty Repair as necessary.
Condition Possible cause Correction / Reference Item
Condition
Possible cause Correction / Reference Item
During compressor 
operation, a rumbling 
noise is heard 
proportional to engine 
revolutions Inadequate clearance in scroll area
Replace compressor.
A loud noise is heard at a 
certain rpm, 
disproportionately to 
engine revolution Loose or faulty compressor drive belt
Adjust drive belt tension or replace drive belt.
Loose compressor mounting bolts Retighten mounting bolts.
A loud rattle is heard at 
low engine rpm Loose compressor clutch plate bolt
Retighten clutch plate bolt.
Replace compressor if it was operated in this 
condition for a long time.
Condition Possible cause Correction / Reference Item
A rumbling noise is heard 
when compressor is not 
in operation Worn or damaged bearings
Replace magnet clutch assembly.
A chattering noise is 
heard when compressor 
is in operation Faulty magnet clutch clearance 
(excessive clearance)
Adjust magnet clutch clearance.
Worn magnet clutch friction surface Replace magnet clutch assembly.
Compressor oil leaked from shaft seal, 
contaminating the friction surface Replace compressor body assembly.
Condition
Possible cause Correction / Reference Item
A droning noise is heard 
from inside of the vehicle, 
but not particularly 
noticeable in engine 
compartment Faulty tubing clamps
Reposition clamps or increase the number of 
clamps.
Resonance caused by pulsation from 
variations in re frigerant pressure Attach a silencer to tubing, or modify its 
position and length.
Condition
Possible cause Correction / Reference Item
Considerable vibration in 
condenser assembly Resonance from condenser assembly 
bracket and body Firmly insert a silenc
er between condenser 
assembly bracket and body.
Condition Possible cause Correction / Reference Item
A large rattling noise is 
heard at idle or sudden 
acceleration Loosen crankshaft pulley bolt
Retighten bolt.  
Page 959 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-11
5) Warm up engine to the normal operating temperature and keep it at the specified idle speed.
6) Turn A/C switch ON, set blower speed selector at  maximum speed position, temperature selector at 
maximum cold position, airflow selector at face 
position, and air intake switch at recirculation 
position. (Confirm that A/C compressor and 
condenser fans are working.)
7) Wait for ten minutes to  stabilize the A/C operation.
8) Open front windows, front doors and engine hood.
9) With about 20 mm (0.8 in.)  of dry bulb thermometer 
(1) put right in front of center ventilation louver and a 
wet and dry bulb thermometer (2) near air inlet of 
HVAC unit. 10) Check for each pressure of low side and high side if 
it is within shaded range of graph. If each gauge 
reading is out of specified pressure, correct defective 
part referring to the following table.
NOTE
Pressure registered on gauge varies with 
ambient temperature. Therefore, use the 
graphs when determining if pressures are 
normal or not.
 
Low side and high side pressure example, 
Gauges should read as follows when ambient 
temperature is 30 °C (86 °F)
Pressure on high pressure gauge (HI): 1590 – 
1940 kPa (15.9 – 19.4 kg/cm2)
Pressure on low pressure gauge (LO): 270 – 430 
kPa (2.7 – 4.3 kg/cm
2)
2
1
I4RS0B720004-01
[A]: Pressure of high pressure gauge
[B]: Pressure of low pressure gauge
[C]: Ambient temperature
[D]: Humidity [E]: Acceptable range
22
312.9 2200
0 1
2 3 30 70 30 70 %
4 5 6 7 8 9
10
11 12 13 14 15
16 17
18
19 21
298.7 2100
20
14.2 28.4 42.7 56.9 71.1 85.3 99.5
113.8 128.0 142.2
151.4
170.6
184.9 199.1
213.3 227.5
241.7
256.0
270.2
284.4
100 200 300 400 500 600 700 800 900
1000 1100 1200
1300
1400 1500 1600
1700 1800
1900
2000
25 30 35
77 86 95
psi kPa     kg/cm
2
 C
 F
“A”
“B”
“C”
“D”
23
2300
327.1
[A]
[B]
[C][D][E]
[E]
I7RS0A721006-01  
Page 960 of 1496

Downloaded from www.Manualslib.com manuals search engine 7B-12 Air Conditioning System: Manual Type
High pressure gauge
Low pressure gaugeCondition Possible cause Correction
Pressure is higher than 
acceptable range
(“A” area) Refrigerant overcharged Recharge.
Expansion valve frozen or clogged Check expansion valve.
Clogged refrigerant passage of high pressure side Clean or replace.
Radiator cooling fan malfunction 
(Insufficient cooling of condenser)
Check radiator cooling fan.
Dirty or bent condenser fins 
(Insufficient cooling of condenser) Clean or repair.
Compressor malfunction (Insuffi cient oil etc.) Check compressor.
Engine overheat Check engine cooling system 
referring to “Engin
e Cooling Symptom 
Diagnosis in Section 1F”.
Pressure is lower than 
acceptable range
(“B” area) Insufficient refrigerant 
(Insufficient charge or leakage)
Check for leakage, repair if necessary 
and recharge.
Expansion valve malfunction 
(valve opens too wide) Check expansion valve.
Compressor malfunction 
(Insufficient compression) Check compressor.
Condition Possible cause Correction
Pressure is higher than 
acceptable range
(“C” area) Expansion valve malfunction 
(valve opens too wide)
Check expansion valve.
Compressor malfunction 
(Insufficient compression) Check compressor.
Pressure is lower than 
acceptable range
(“D” area) Insufficient refrigerant 
(Insufficient charge or leakage)
Check for leakage, repair if necessary 
and recharge.
Expansion valve malfunction 
(valve opens too narrow) Check expansion valve.
Clogged refrigerant passage (crashed pipe) Repair or replace.  
Page 961 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-13
11) Check inlet port temperature-to-outlet port temperature relationship using the graph. For example, if temperature 
near air inlet of HVAC unit is 30  °C (86  °F) and the one at air outlet of  center ventilation louver is 17  °C (62.6  °F), 
their crossing point is within acceptable range as shown in the graph. In this case, cooling performance is 
satisfactory and proper.
12) If crossing point is out of acceptable range,  diagnose trouble referring to the following table.
Thermometer at center duct
NOTE
If ambient temperature is approximately 30  °C (86  °F), it is possible to diagnose A/C system in detail 
referring to the following table.
 
[A]: Temp at air outlet of center ventilation louver [C]: Humidity
[B]: Temp near air inlet of HVAC unit [D]: Acceptable range
ConditionPossible cause Correction
Crossing point is higher 
than acceptable range 
(“E” area) Insufficient or excessive charge of refrigerant Check refrigerant pressure.
Dirty or bent A/C evaporator fins
Clean or repair.
Air leakage from cooling (heater) unit or air duct Repair or replace.
Malfunctioning, switch over function of door in 
cooling (heater) unit Repair or replace.
Compressor malfunct ion Check compressor.
Crossing point is lower 
than acceptable range 
(“F” area) Insufficient air volume from center duct 
(Heater blower malfunction)
Check blower motor and fan.
Compressor malfunct ion Check compressor.
8 9
10 11 12 13 14
15 16 17 18 19
20
21
22
23
24
25 26
27
28
46.4 48.2 50.0 51.8 53.6 55.4 57.2 59.0 60.8 62.6 64.4
66.2 68.0
69.8
71.6
73.4
75.2
77.0
78.8 80.6
82.4
25 30 35
77 86 95
  F        C
 C
 F
“E”
“F”30 70 %
[A]
[B][C]
[D]
I7RS0A721007-01  
Page 962 of 1496

Downloaded from www.Manualslib.com manuals search engine 7B-14 Air Conditioning System: Manual Type
ConditionPossible cause Correction
Manifold gauge MPa (kg/cm2) (psi)
Detail
Lo Hi
0.27 – 0.43
(2.7 – 4.3)
(38 – 61) 1.59 – 1.94
(15.9 – 19.4)
(226 – 276)
Normal condition — —
Negative pressure 0.5 – 0.6
(5 – 6)
(71.2 – 85.3) The low pressure side 
reads a negative 
pressure, and the high 
pressure side reads an 
extremely low pressure.
Presence of frost around 
tubing to and from 
receiver/dryer and 
expansion valve. Dust particles or water 
droplets are either 
stuck or frozen inside 
expansion valve, 
preventing the 
refrigerant from 
flowing.Clean expansion 
valve.
Replace it if it cannot 
be cleaned.
Replace receiver/
dryer.
Evacuate the A/C 
system and recharge 
with fresh refrigerant.
Normal:
0.27 – 0.43
(2.7 – 4.3)
(38 – 61)
↑  ↓
Abnormal:
Negative pressure Normal:
1.59 – 1.94
(15.9 – 19.4)
(226 – 276)
↑
 ↓
Abnormal:
0.7 – 1.0
(7 – 10)
(100 – 142) During A/C operation, the 
low pressure side 
sometimes indicates 
negative pressure, and 
sometimes normal 
pressure. Also high 
pressure side reading 
fluctuates between the 
abnormal and normal 
pressure.
Expansion valve is 
frozen due to 
moisture in the 
system, and 
temporarily shuts off 
the refrigeration cycle.
Replace expansion 
valve.
Replace receiver/
dryer.
Evacuate A/C system 
and recharge with 
fresh refrigerant.
0.05 – 0.15
(0.5 – 1.5)
(4.2 – 21.3) 0.7 – 1.0
(7 – 10)
(100 – 142) Both low and high 
pressure sides indicate 
low readings.
Output air is slightly cold.
Insufficient refrigerant 
in system
(Refrigerant leaking).Using leak detector, 
check for leaks and 
repair as necessary.
Recharge refrigerant 
to a specified amount.
If the pressure reading 
is almost 0 when the 
manifold gauges are 
attached, check for 
any leaks, repair 
them, and evacuate 
the system.
0.4 – 0.6
(4 – 6)
(56.9 – 85.3) Pressure on low pressure 
side is high.
Pressure on high 
pressure side is low.
Both pressure becoming 
equal right after A/C is 
turned OFF.
Internal leak in 
compressor.
Inspect compressor 
and repair or replace 
as necessary.  
Page 963 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-15
A/C System Inspection at ECMS7RS0B7214004
Voltage Check
When checking voltage at ECM connector terminals related to A/C system, refer to “DTC P2101: Throttle Actuator 
Control Motor Circuit Range /  Performance in Section 1A”.
0.40 – 0.45
(4.0 – 4.5)
(57 – 64)
2.0 – 2.5
(20 – 25)
(285 – 355) High pressure reading on 
both low and high 
pressure sides.
Overcharged A/C 
system.
Adjust refrigerant to 
specified amount.
Faulty condenser 
cooling operation. Clean condenser.
Faulty radiator cooling 
fan operation. Inspect and repair 
radiator cooling fan.
High pressure reading on 
both low and high 
pressure sides.
Low pressure side tubing 
is not cold when touched. Presence of air in A/C 
system
(Improperly 
evacuated).Replace receiver/
dryer.
Inspect quantity of 
compressor oil and 
presence of 
contaminants in oil.
Evacuate system and 
recharge with fresh 
refrigerant.
0.45 – 0.55
(4.5 – 5.5)
(64 – 78) High pressure reading on 
both low and high 
pressure sides.
Large amount of frost or 
dew on the low pressure 
side tubing.Faulty expansion 
valve.
Refrigerant flow is not 
regulated properly.
Replace expansion 
valve.
Condition
Possible cause Correction
Manifold gauge MPa (kg/cm
2) (psi)
Detail
Lo Hi  
Page 965 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-17
NOTE
• After recovering refrigerant from system, the amount of removed compressor oil must be measured 
for replenishing compressor oil.
• When handling recovery and recycling equipment, be sure to follow the instruction manual for the  equipment.
 
Replenishing Compressor Oil
It is necessary to replenish specified amount of 
compressor oil to compressor  from compressor suction 
side hole (1) before evacuating and charging refrigerant.
When charging refrigerant only
When charging refrigerant without replacing any 
component, replenish the same amount of measured oil 
when recovering refrigerant (if not measure, replenish 10 
cm
3 (10 ml, 0.34 US. oz, 0.35 Imp. oz) oil).
When replacing compressor
CAUTION! 
Be sure to use specified compressor oil or an 
equivalent compressor oil.
 
Compressor oil is sealed in each new compressor by the 
amount required for A/C system. Therefore, when using 
a new compressor, drain the calculated amount of oil 
from it. “C” = “A” – “B”
“C”: Amount of oil to be drained
“A”: Amount of oil in a new compressor
“B”: Amount of oil in removed compressor
NOTE
Compressor assembly su
pplied from factory 
is filled up with the following amount of oil.
 
:  Compressor oil 99000–99015–00A 
(MATSUSHITADENKI GU10) 
Oil amount in compressor
 90  ± 5 cm3 (90  ± 5 ml, 3.04  ± 0.17 US. oz, 3.17 ± 0.18 
Imp. oz)
I4RS0A720012-01
1
I4RS0B720007-01
1. New compressor 2. Removed compressor
I2RH01720015-01  
Page 966 of 1496

Downloaded from www.Manualslib.com manuals search engine 7B-18 Air Conditioning System: Manual Type
When replacing other parts
Replenish the following amount of oil to compressor.
Amount of compressor oil to be replenished
Evaporator: 25 cm3 (25 ml, 0.85 US. oz, 0.88 Imp. oz)
Condenser: 15 cm3 (15 ml, 0.51 US. oz, 0.53 Imp. oz)
Receiver/dryer: 10 cm3 (10 ml, 0.34 US. oz, 0.35 lmp. 
oz)
Hoses: 10 cm
3 (10 ml, 0.34 US. oz, 0.35 Imp. oz) each
Pipes: 10 cm3 (10 ml, 0.34 US. oz, 0.35 Imp. oz) each
Evacuation
CAUTION! 
Do not evacuate before recovering 
refrigerant in A/C system.
 
NOTE
Once air conditioning system circuit is 
opened (exposed) to atmospheric air, system 
must be evacuated by using a vacuum pump. 
The A/C system should be attached with a 
manifold gauge set, and should be evacuated 
for approximately 15 minutes.
 
1) Connect high charging hose (1) and low charging  hose (2) of manifold gauge set (3) respectively as 
follows:
High charging hose  → High pressure charging valve 
(4) on condenser outlet pipe
Low charging hose  → Low pressure charging valve 
(5) on suction pipe
2) Attach center charging hose (6) of manifold gauge  set to vacuum pump (7).
3) Operate vacuum pump,  and then open discharge 
side valve (Hi) (8) of manifold gauge set.
If there is no blockage in  the system, there will be an 
indication on high pressure gauge (9).
In this case, open the other side valve (Lo) (10) of 
the set and repair the system.
4) Approximately 10 minutes later, low pressure gauge  (11) should show a vacuum lower than –100 kPa (–
1.0 kg/cm
2, –760 mmHg, –14.7 psi) providing no 
leakage exists.
NOTE
• If the system does not show a vacuum  below –100 kPa (–1.0 kg/cm
2, –760 mmHg, 
–14.7 psi), close both valves, stop vacuum 
pump and watch movement of low 
pressure gauge.
• Increase in the gauge reading suggests  existence of leakage. In this case, repair 
the system before continuing its 
evacuation.
• If the gauge shows a stable reading  (suggesting no leakage), continue 
evacuation.
 
5) Evacuation should be carried out for a total of at  least 15 minutes.
6) Continue evacuation until low pressure gauge  indicates a vacuum less than –100 kPa (–1.0 kg/cm
2, 
–760 mmHg, –14.7 psi), and then close both valves.
7) Stop vacuum pump. Disconnect center charging  hose from pump inlet. No w, the system is ready for 
charging refrigerant.
Checking A/C System for Pressure Leaks
After completing the evacuation, close manifold gauge 
high pressure valve and low pressure valve and wait 10 
minutes. Verify that low pressure gauge reading has not 
changed.
CAUTION! 
If the gauge reading moves closer to “0”, 
there is a leak somewhere. Inspect the tubing 
connections and make necessary 
corrections. And then, evacuate system once 
again and make sure that there are no leaks.
 
7 5
2
4
1
10
11
3
9 8
6
I4RS0A720014-01  
Page 967 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-19
Charge
CAUTION! 
• Because the sight glass is not used for this A/C system, do not perform an additional 
charge to the A/C system. To charge the 
proper amount of refrigerant, recover and 
evacuate the A/C system first. And then, 
charge the proper amount of refrigerant 
into the A/C system.
• Always charge refrigerant through low  pressure side of A/C system after the initial 
charge is performed from the high 
pressure side with the engine stopped.
• Never charge refrigerant through high  pressure side of A/C system with engine 
running.
• Do not charge refrigerant while  compressor is hot.
• When installing tap valve to refrigerant  container to make a hole there through, 
carefully follow dire ctions given by 
manufacturer.
• A pressure gauge should always be used  before and during refrigerant charge.
• The refrigerant container should be  emptied of refrigerant  when discarding it.
• The refrigerant container should not be  heated up to 40  °C (104  °F) or over.
• Refrigerant container should not be  reversed in direction during refrigerant 
charge. Reversing in direction causes 
liquid refrigerant to enter compressor, 
causing troubles, such as compression of 
liquid refrigerant and the like.
 
NOTE
The air conditioning system contains HFC-
134a (R-134a).
Described here is a method to charge the air 
conditioning system with refrigerant from the 
refrigerant service container.
When charging refrigerant recovered by 
using the refrigerant and recycling 
equipment (when recycling refrigerant), 
follow the procedure described in the 
equipment manufacturer’s instruction 
manual.
 
Charge proper amount of refrigerant accurately in 
accordance with the following procedure.
Specified amount of refrigerant
370  ± 20 g (13.0 ± 0.7 oz)
The initial charge of the  A/C system is performed 
through the high pressure side with the engine stopped.
And next, this method must be followed by charging from 
the low pressure side with the engine running.
1) Check if hoses are routed properly after evacuating  the system.
2) Connect low charging hose (1) and high charging  hose (2) of the manifold gauge set (3) in position. 
Then, open refrigerant container valve (4) to purge 
the charging line.
3) Open the high pressure side valve (5) and charge  refrigerant to system.
4) After a while, open the low pressure side valve (6)  and close the high pressure side valve.
WARNING! 
Make sure that high pressure side valve is 
closed securely.
 
5) Start engine and keep engine speed at 1500 r/min, and then operate A/C system.
6) Charge A/C system with refrigerant in vapor state. At  this time, refrigerant container should be held 
upright.
1
2 6 3
5 4
I4RS0A720015-01