TROUBLE DIAGNOSIS
ATC-71
C
D
E
F
G
H
I
K
L
MA
B
AT C
Revision: 2006 November2007 350Z
Blower Speed Compensation
Sunload
When the in-vehicle temperature and the set temperature are very close, the blower will be operating at low
speed. The low speed will vary depending on the sunload. During conditions of low or no sunload, the blower
speed is at duty ratio 25%. During high sunload conditions, the unified meter and A/C amp. raise the blower
speed.(duty ratio 49%).
Fan Speed Control Specification
COMPONENT DESCRIPTION
Brush-less Motor
The blower motor utilizes a brush-less motor with a rotating magnet.
Quietness is improved over previous motors where the brush was
the point of contact and the coil rotated.
DIAGNOSIS PROCEDURE FOR BLOWER MOTOR
SYMPTOM: Blower motor operation is malfunctioning.
RJIA1996E
ZHA152H
SJIA0266E
Page 72 of 142
ATC-72
TROUBLE DIAGNOSIS
Revision: 2006 November2007 350Z
1. CHECK POWER SUPPLY FOR BLOWER MOTOR
1. Disconnect blower motor connector.
2. Turn ignition switch ON.
3. Check voltage between blower motor harness connector M62
terminal 1 and ground.
OK or NG
OK >> GO TO 2.
NG >> Check power supply circuit and 15A fuses [Nos. 10 and
11, located in the fuse block (J/B)]. Refer to PG-85,
"FUSE BLOCK - JUNCTION BOX (J/B)" .
If fuse are OK, check harness for open circuit. Repair or replace if necessary.
If fuse are NG, check harness for short circuit and replace fuse.
2. CHECK GROUND CIRCUIT FOR BLOWER MOTOR
1. Turn ignition switch OFF.
2. Check continuity between blower motor harness connector M62
terminal 3 and ground.
OK or NG
OK >> GO TO 3.
NG >> Repair harness or connector.
3. CHECK CIRCUIT CONTINUITY BETWEEN BLOWER MOTOR AND UNIFIED METER AND A/C AMP.
1. Disconnect unified meter connector and A/C amp. connector.
2. Check continuity between blower motor harness connector M62
terminal 2 and unified meter and A/C amp. harness connector
M50 terminal 53.
OK or NG
OK >> GO TO 4.
NG >> Repair harness or connector.1 – Ground : Battery voltage
RJIA1997E
3 – Ground : Continuity should exist.
RJIA1998E
2 – 53 : Continuity should exist.
RJIA1999E
Page 73 of 142
TROUBLE DIAGNOSIS
ATC-73
C
D
E
F
G
H
I
K
L
MA
B
AT C
Revision: 2006 November2007 350Z
4. CHECK UNIFIED METER AND A/C AMP. OUTPUT SIGNAL
1. Reconnect blower motor connector and unified meter and A/C
amp. connector.
2. Turn ignition switch ON.
3. Change the fan speed from Lo to Hi, and check the duty ratios
between blower motor harness connector M62 terminal 2 and
ground by using an oscilloscope. Normal terminal 2 drive signal
duty ratios are shown in the table below.
OK or NG
OK >> Replace blower motor after confirming the fan air flow does not change.
NG >> Replace unified meter and A/C amp.
COMPONENT INSPECTION
Blower Motor
Confirm smooth rotation of the blower motor.
Ensure that there are no foreign particles inside the blower unit.
RJIA2000E
RJIA1390E
RJIA0905E
Page 74 of 142
ATC-74
TROUBLE DIAGNOSIS
Revision: 2006 November2007 350Z
Magnet Clutch CircuitNJS00015
SYMPTOM: Magnet clutch does not engage.
INSPECTION FLOW
*1ATC-46, "FUNCTION CONFIRMA-
TION PROCEDURE", see No. 1.*2ATC-92, "
Ambient Sensor Circuit"*3AT C - 4 6 , "FUNCTION CONFIRMA-
TION PROCEDURE", see No. 9.
*4ATC-75, "
DIAGNOSIS PROCE-
DURE FOR MAGNET CLUTCH"
*5ATC-86, "TROUBLE DIAGNOSIS
FOR UNUSUAL PRESSURE"
*6AT C - 5 3 , "Operational Check"
*7ATC-46, "FUNCTION CONFIRMA-
TION PROCEDURE", see No. 5 to 7.*8ATC-34, "
SYMPTOM TABLE"*9ATC-100, "Intake Sensor Circuit"
SJIA1129E
Page 75 of 142
TROUBLE DIAGNOSIS
ATC-75
C
D
E
F
G
H
I
K
L
MA
B
AT C
Revision: 2006 November2007 350Z
SYSTEM DESCRIPTION
Unified meter and A/C amp. controls compressor operation by ambient temperature, intake air temperature
and signal from ECM.
Low Temperature Protection Control
Unified meter and A/C amp. will turn compressor ON or OFF as determined by a signal detected by ambient
sensor and intake sensor.
When ambient temperature is higher than −2°C (28°F), the compres-
sor turns ON. The compressor turns OFF when ambient temperature
is lower than −5°C (23°F).
When intake air temperature is higher than 1°C (34°F), the compres-
sor turns ON. The compressor turns OFF when intake air tempera-
ture is lower than −5°C (23°F).
DIAGNOSIS PROCEDURE FOR MAGNET CLUTCH
SYMPTOM: Magnet clutch does not engage when A/C switch is ON.
RHA094GB
SJIA0267E
SJIA1891E
Page 76 of 142
ATC-76
TROUBLE DIAGNOSIS
Revision: 2006 November2007 350Z
1. CHECK AMBIENT SENSOR CIRCUIT AND INTAKE SENSOR CIRCUIT
Check ambient sensor and intake sensor. Refer to AT C - 4 6 , "
FUNCTION CONFIRMATION PROCEDURE" ,
see No. 9.
OK or NG
OK >> GO TO 2.
NG >>
Malfunctioning ambient sensor: Refer to AT C - 9 2 , "Ambient Sensor Circuit" .
Malfunctioning intake sensor: Refer to ATC-100, "Intake Sensor Circuit" .
2. PERFORM AUTO ACTIVE TEST
Refer to PG-20, "
Auto Active Test" .
Dose the magnet clutch operate?
YES >> WITH CONSULT-III: GO TO 5.
WITHOUT CONSULT-III: GO TO 6.
NO >> Check 10A fuse (No. 79, located in IPDM E/R), and GO TO 3. Refer to PG-23, "
IPDM E/R Termi-
nal Arrangement" .
3. CHECK CIRCUIT CONTINUITY BETWEEN IPDM E/R AND COMPRESSOR
1. Turn ignition switch OFF.
2. Disconnect IPDM E/R connector and compressor connector.
3. Check continuity between IPDM E/R harness connector E8 ter-
minal 33 and compressor harness connector F24 terminal 1.
OK or NG
OK >> GO TO 4.
NG >> Repair harness or connector.
4. CHECK MAGNET CLUTCH CIRCUIT
Check for operation sound when applying battery voltage direct cur-
rent to terminal.
OK or NG
OK >> 1. Replace IPDM E/R.
2. Go to self-diagnosis procedure AT C - 4 6 , "
FUNCTION
CONFIRMATION PROCEDURE" and preform self-
diagnosis STEP-4. Confirm that magnet clutch opera-
tion normal.
NG >> 1. Replace magnet clutch.
2. Go to self-diagnosis procedure AT C - 4 6 , "
FUNCTION
CONFIRMATION PROCEDURE" and preform self-
diagnosis STEP-4. Confirm that magnet clutch operation normal.
5. CHECK BCM INPUT (COMPRESSOR ON) SIGNAL
Check compressor ON/OFF signal. Refer to AT C - 3 3 , "
CONSULT-III Function (BCM)" .
OK or NG
OK >> GO TO 8.
NG >> GO TO 6.
33 – 1 : Continuity should exist.
RJIA2004E
RJIA2005E
A/C SW ON : AIR COND SIG ON
A/C SW OFF : AIR COND SIG OFF
Page 77 of 142
TROUBLE DIAGNOSIS
ATC-77
C
D
E
F
G
H
I
K
L
MA
B
AT C
Revision: 2006 November2007 350Z
6. CHECK CIRCUIT CONTINUITY BETWEEN BCM AND UNIFIED METER AND A/C AMP.
1. Turn ignition switch OFF.
2. Disconnect BCM connector and unified meter and A/C amp.
connector.
3. Check continuity between BCM harness connector M90 terminal
27 and unified meter and A/C amp. harness connector M50 ter-
minal 42.
OK or NG
OK >> GO TO 7.
NG >> Repair harness or connector.
7. CHECK VOLTAGE FOR UNIFIED METER AND A/C AMP. (COMPRESSOR ON SIGNAL)
1. Reconnect BCM connector and unified meter and A/C amp.
connector.
2. Turn ignition switch ON.
3. Check voltage between unified meter and A/C amp. harness
connector M50 terminal 42 and ground.
OK or NG
OK >> GO TO 8.
NG-1 >> If the voltage is approx. 5 V when A/C switch is ON: Replace unified meter and A/C amp.
NG-2 >> If the voltage is approx. 0 V when A/C switch is OFF: Replace BCM.27 – 42 : Continuity should exist.
RJIA2006E
Terminals
Condition Voltage (+)
(−) Unified meter
and A/C amp.
connectorTerminal No.
M50 42 GroundA/C switch: ON
(Blower motor oper-
ates.)Approx. 0 V
A/C switch: OFF Approx. 5 V
RJIA2007E
Page 78 of 142
ATC-78
TROUBLE DIAGNOSIS
Revision: 2006 November2007 350Z
8. CHECK REFRIGERANT PRESSURE SENSOR
WITH CONSULT-III
1. Start the engine.
2. Check voltage of refrigerant pressure sensor. Refer to EC-127, "
CONSULT-III Reference Value in Data
Monitor" .
WITHOUT CONSULT-III
1. Start the engine.
2. Check voltage between ECM harness connector M71 terminal 105 and ground.
OK or NG
OK >> WITH CONSULT-III: GO TO 9.
WITHOUT CONSULT-III: GO TO 10.
NG >> Refer to EC-710, "
REFRIGERANT PRESSURE SENSOR" .
9. CHECK BCM INPUT (FAN ON) SIGNAL
Check FAN ON/OFF signal. Refer to AT C - 3 3 , "
CONSULT-III Function (BCM)" .
OK or NG
OK >> GO TO 12.
NG >> GO TO 10.
10. CHECK CIRCUIT CONTINUITY BETWEEN BCM AND UNIFIED METER AND A/C AMP.
1. Turn ignition switch OFF.
2. Disconnect BCM connector and unified meter and A/C amp.
connector.
3. Check continuity between BCM harness connector M90 terminal
28 and unified meter and A/C amp. harness connector M50 ter-
minal 57.
OK or NG
OK >> GO TO 11.
NG >> Repair harness or connector.
Terminals
Condition Voltage (+)
(−)
ECM con-
nectorTerminal No.
M71 105 GroundA/C switch: ON
(Blower motor
operates.)Approx. 1.0 - 4.0 V
FAN SW ON : HEATER FAN SW ON
FAN SW OFF : HEATER FAN SW OFF
28 – 57 : Continuity should exist.
RJIA2009E
Page 79 of 142
TROUBLE DIAGNOSIS
ATC-79
C
D
E
F
G
H
I
K
L
MA
B
AT C
Revision: 2006 November2007 350Z
11 . CHECK VOLTAGE FOR UNIFIED METER AND A/C AMP. (FAN ON SIGNAL)
1. Reconnect BCM connector and unified meter and A/C amp.
connector.
2. Turn ignition switch ON.
3. Check voltage between unified meter and A/C amp. harness
connector M50 terminal 57 and ground.
OK or NG
OK >> GO TO 12.
NG-1 >> If the voltage is approx. 5 V when blower motor is ON: Replace unified meter and A/C amp.
NG-2 >> If the voltage is approx. 0 V when blower motor is OFF: Replace BCM.
12. CHECK CAN COMMUNICATION
Check CAN communication. Refer to BCS-16, "
CAN Communication Inspection Using CONSULT-III (Self-
Diagnosis)" .
BCM – ECM
ECM – IPDM E/R
ECM – Unified meter and A/C amp.
OK or NG
OK >> Replace ECM.
NG >> Repair or replace malfunctioning part(s).
Terminals
Condition Voltage (+)
(−) Unified meter
and A/C amp.
connectorTerminal No.
M50 57 GroundFan control dial: ON
(Blower motor oper-
ates.)Approx. 0 V
Fan control dial: OFF Approx. 5 V
RJIA2010E
Page 80 of 142
ATC-80
TROUBLE DIAGNOSIS
Revision: 2006 November2007 350Z
COMPONENT INSPECTION
Refrigerant Pressure Sensor
The refrigerant pressure sensor is attached to the liquid tank.
Make sure that the A/C refrigerant pressure and the sensor output
voltage are within the specified range as shown in the A/C operating
condition figure. Refer to EC-710, "
REFRIGERANT PRESSURE
SENSOR" .
RJIA1393E
SJIA1841E