air cond SUZUKI SWIFT 2005 2.G Service Workshop Manual
[x] Cancel search | Manufacturer: SUZUKI, Model Year: 2005, Model line: SWIFT, Model: SUZUKI SWIFT 2005 2.GPages: 1496, PDF Size: 34.44 MB
Page 960 of 1496

Downloaded from www.Manualslib.com manuals search engine 7B-12 Air Conditioning System: Manual Type
High pressure gauge
Low pressure gaugeCondition Possible cause Correction
Pressure is higher than 
acceptable range
(“A” area) Refrigerant overcharged Recharge.
Expansion valve frozen or clogged Check expansion valve.
Clogged refrigerant passage of high pressure side Clean or replace.
Radiator cooling fan malfunction 
(Insufficient cooling of condenser)
Check radiator cooling fan.
Dirty or bent condenser fins 
(Insufficient cooling of condenser) Clean or repair.
Compressor malfunction (Insuffi cient oil etc.) Check compressor.
Engine overheat Check engine cooling system 
referring to “Engin
e Cooling Symptom 
Diagnosis in Section 1F”.
Pressure is lower than 
acceptable range
(“B” area) Insufficient refrigerant 
(Insufficient charge or leakage)
Check for leakage, repair if necessary 
and recharge.
Expansion valve malfunction 
(valve opens too wide) Check expansion valve.
Compressor malfunction 
(Insufficient compression) Check compressor.
Condition Possible cause Correction
Pressure is higher than 
acceptable range
(“C” area) Expansion valve malfunction 
(valve opens too wide)
Check expansion valve.
Compressor malfunction 
(Insufficient compression) Check compressor.
Pressure is lower than 
acceptable range
(“D” area) Insufficient refrigerant 
(Insufficient charge or leakage)
Check for leakage, repair if necessary 
and recharge.
Expansion valve malfunction 
(valve opens too narrow) Check expansion valve.
Clogged refrigerant passage (crashed pipe) Repair or replace.  
Page 961 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-13
11) Check inlet port temperature-to-outlet port temperature relationship using the graph. For example, if temperature 
near air inlet of HVAC unit is 30  °C (86  °F) and the one at air outlet of  center ventilation louver is 17  °C (62.6  °F), 
their crossing point is within acceptable range as shown in the graph. In this case, cooling performance is 
satisfactory and proper.
12) If crossing point is out of acceptable range,  diagnose trouble referring to the following table.
Thermometer at center duct
NOTE
If ambient temperature is approximately 30  °C (86  °F), it is possible to diagnose A/C system in detail 
referring to the following table.
 
[A]: Temp at air outlet of center ventilation louver [C]: Humidity
[B]: Temp near air inlet of HVAC unit [D]: Acceptable range
ConditionPossible cause Correction
Crossing point is higher 
than acceptable range 
(“E” area) Insufficient or excessive charge of refrigerant Check refrigerant pressure.
Dirty or bent A/C evaporator fins
Clean or repair.
Air leakage from cooling (heater) unit or air duct Repair or replace.
Malfunctioning, switch over function of door in 
cooling (heater) unit Repair or replace.
Compressor malfunct ion Check compressor.
Crossing point is lower 
than acceptable range 
(“F” area) Insufficient air volume from center duct 
(Heater blower malfunction)
Check blower motor and fan.
Compressor malfunct ion Check compressor.
8 9
10 11 12 13 14
15 16 17 18 19
20
21
22
23
24
25 26
27
28
46.4 48.2 50.0 51.8 53.6 55.4 57.2 59.0 60.8 62.6 64.4
66.2 68.0
69.8
71.6
73.4
75.2
77.0
78.8 80.6
82.4
25 30 35
77 86 95
  F        C
 C
 F
“E”
“F”30 70 %
[A]
[B][C]
[D]
I7RS0A721007-01  
Page 962 of 1496

Downloaded from www.Manualslib.com manuals search engine 7B-14 Air Conditioning System: Manual Type
ConditionPossible cause Correction
Manifold gauge MPa (kg/cm2) (psi)
Detail
Lo Hi
0.27 – 0.43
(2.7 – 4.3)
(38 – 61) 1.59 – 1.94
(15.9 – 19.4)
(226 – 276)
Normal condition — —
Negative pressure 0.5 – 0.6
(5 – 6)
(71.2 – 85.3) The low pressure side 
reads a negative 
pressure, and the high 
pressure side reads an 
extremely low pressure.
Presence of frost around 
tubing to and from 
receiver/dryer and 
expansion valve. Dust particles or water 
droplets are either 
stuck or frozen inside 
expansion valve, 
preventing the 
refrigerant from 
flowing.Clean expansion 
valve.
Replace it if it cannot 
be cleaned.
Replace receiver/
dryer.
Evacuate the A/C 
system and recharge 
with fresh refrigerant.
Normal:
0.27 – 0.43
(2.7 – 4.3)
(38 – 61)
↑  ↓
Abnormal:
Negative pressure Normal:
1.59 – 1.94
(15.9 – 19.4)
(226 – 276)
↑
 ↓
Abnormal:
0.7 – 1.0
(7 – 10)
(100 – 142) During A/C operation, the 
low pressure side 
sometimes indicates 
negative pressure, and 
sometimes normal 
pressure. Also high 
pressure side reading 
fluctuates between the 
abnormal and normal 
pressure.
Expansion valve is 
frozen due to 
moisture in the 
system, and 
temporarily shuts off 
the refrigeration cycle.
Replace expansion 
valve.
Replace receiver/
dryer.
Evacuate A/C system 
and recharge with 
fresh refrigerant.
0.05 – 0.15
(0.5 – 1.5)
(4.2 – 21.3) 0.7 – 1.0
(7 – 10)
(100 – 142) Both low and high 
pressure sides indicate 
low readings.
Output air is slightly cold.
Insufficient refrigerant 
in system
(Refrigerant leaking).Using leak detector, 
check for leaks and 
repair as necessary.
Recharge refrigerant 
to a specified amount.
If the pressure reading 
is almost 0 when the 
manifold gauges are 
attached, check for 
any leaks, repair 
them, and evacuate 
the system.
0.4 – 0.6
(4 – 6)
(56.9 – 85.3) Pressure on low pressure 
side is high.
Pressure on high 
pressure side is low.
Both pressure becoming 
equal right after A/C is 
turned OFF.
Internal leak in 
compressor.
Inspect compressor 
and repair or replace 
as necessary.  
Page 963 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-15
A/C System Inspection at ECMS7RS0B7214004
Voltage Check
When checking voltage at ECM connector terminals related to A/C system, refer to “DTC P2101: Throttle Actuator 
Control Motor Circuit Range /  Performance in Section 1A”.
0.40 – 0.45
(4.0 – 4.5)
(57 – 64)
2.0 – 2.5
(20 – 25)
(285 – 355) High pressure reading on 
both low and high 
pressure sides.
Overcharged A/C 
system.
Adjust refrigerant to 
specified amount.
Faulty condenser 
cooling operation. Clean condenser.
Faulty radiator cooling 
fan operation. Inspect and repair 
radiator cooling fan.
High pressure reading on 
both low and high 
pressure sides.
Low pressure side tubing 
is not cold when touched. Presence of air in A/C 
system
(Improperly 
evacuated).Replace receiver/
dryer.
Inspect quantity of 
compressor oil and 
presence of 
contaminants in oil.
Evacuate system and 
recharge with fresh 
refrigerant.
0.45 – 0.55
(4.5 – 5.5)
(64 – 78) High pressure reading on 
both low and high 
pressure sides.
Large amount of frost or 
dew on the low pressure 
side tubing.Faulty expansion 
valve.
Refrigerant flow is not 
regulated properly.
Replace expansion 
valve.
Condition
Possible cause Correction
Manifold gauge MPa (kg/cm
2) (psi)
Detail
Lo Hi  
Page 964 of 1496

Downloaded from www.Manualslib.com manuals search engine 7B-16 Air Conditioning System: Manual Type
Repair Instructions
Operation Procedure for Refrigerant ChargeS7RS0B7216001
WARNING! 
• Your eyes should not be exposed to refrigerant (liquid).Any liquid HFC-134a (R-134a) escaping by accident shows a temperature as low as approximately –
6 °C (21.2 ° F) below freezing point. Should liquid HFC-134a  (R-134a) is exposed to your eyes, it may 
cause a serious injury. To protect your eyes from such accident, it is necessary to always wear 
goggles. Should it occur that HFC-134a (R-134a)  is exposed to your eyes, consult a doctor 
immediately.
– Do not use your hand to rub the affected eye(s). Instead, use fresh cold water to splash it over the  affected area to gradually raise temperature of such area above freezing point.
– Obtain proper treatment as soon as possible from a doctor or eye specialist.
• Should the liquid refrigerant HFC-134a (R-134a) is exposed to your skin, the affected area should be  treated in the same manner as when skin is frostbitten or frozen.
• Do not handle refrigerant near any place where welding or steam cleaning is performed.
• Refrigerant should be kept in a cold and dark pl ace. It should never be stored in any place where 
temperature is high, e.g. where exposed to direct su n light, close to fire or inside vehicle (including 
trunk room).
• Avoid breathing fume produced when HFC-134a (R-134a) is burned. Such fume may be hazardous to  your health.
 
Recovery
When discharging refrigerant out of A/C system, always  recover it by using refrigerant recovery and recycling 
equipment because discharging refrigerant HFC-134a (R-1 34a) into atmosphere would cause adverse effect to 
environments.
Start evacuation.Start evacuation.
Stop evacuation.Stop evacuation.
Wait 10 minutesWait 10 minutes
Check A/C system forCheck A/C system for
pressure tighteness.pressure tighteness.
Recharge A/C system withRecharge A/C system withrefrigerant.refrigerant.
Check A/C system for refrigerantCheck A/C system for refrigerantleaks and amount of refrigerantleaks and amount of refrigerantcharged.charged.
Performance testPerformance test
Inspect and repair connections.Inspect and repair connections.
If gauge showsIf gauge showsabnormal conditionsabnormal conditions
Recharge 370    20 g ofRecharge 370    20 g ofrefrigerant.refrigerant.
I5RS0C721005-01  
Page 965 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-17
NOTE
• After recovering refrigerant from system, the amount of removed compressor oil must be measured 
for replenishing compressor oil.
• When handling recovery and recycling equipment, be sure to follow the instruction manual for the  equipment.
 
Replenishing Compressor Oil
It is necessary to replenish specified amount of 
compressor oil to compressor  from compressor suction 
side hole (1) before evacuating and charging refrigerant.
When charging refrigerant only
When charging refrigerant without replacing any 
component, replenish the same amount of measured oil 
when recovering refrigerant (if not measure, replenish 10 
cm
3 (10 ml, 0.34 US. oz, 0.35 Imp. oz) oil).
When replacing compressor
CAUTION! 
Be sure to use specified compressor oil or an 
equivalent compressor oil.
 
Compressor oil is sealed in each new compressor by the 
amount required for A/C system. Therefore, when using 
a new compressor, drain the calculated amount of oil 
from it. “C” = “A” – “B”
“C”: Amount of oil to be drained
“A”: Amount of oil in a new compressor
“B”: Amount of oil in removed compressor
NOTE
Compressor assembly su
pplied from factory 
is filled up with the following amount of oil.
 
:  Compressor oil 99000–99015–00A 
(MATSUSHITADENKI GU10) 
Oil amount in compressor
 90  ± 5 cm3 (90  ± 5 ml, 3.04  ± 0.17 US. oz, 3.17 ± 0.18 
Imp. oz)
I4RS0A720012-01
1
I4RS0B720007-01
1. New compressor 2. Removed compressor
I2RH01720015-01  
Page 966 of 1496

Downloaded from www.Manualslib.com manuals search engine 7B-18 Air Conditioning System: Manual Type
When replacing other parts
Replenish the following amount of oil to compressor.
Amount of compressor oil to be replenished
Evaporator: 25 cm3 (25 ml, 0.85 US. oz, 0.88 Imp. oz)
Condenser: 15 cm3 (15 ml, 0.51 US. oz, 0.53 Imp. oz)
Receiver/dryer: 10 cm3 (10 ml, 0.34 US. oz, 0.35 lmp. 
oz)
Hoses: 10 cm
3 (10 ml, 0.34 US. oz, 0.35 Imp. oz) each
Pipes: 10 cm3 (10 ml, 0.34 US. oz, 0.35 Imp. oz) each
Evacuation
CAUTION! 
Do not evacuate before recovering 
refrigerant in A/C system.
 
NOTE
Once air conditioning system circuit is 
opened (exposed) to atmospheric air, system 
must be evacuated by using a vacuum pump. 
The A/C system should be attached with a 
manifold gauge set, and should be evacuated 
for approximately 15 minutes.
 
1) Connect high charging hose (1) and low charging  hose (2) of manifold gauge set (3) respectively as 
follows:
High charging hose  → High pressure charging valve 
(4) on condenser outlet pipe
Low charging hose  → Low pressure charging valve 
(5) on suction pipe
2) Attach center charging hose (6) of manifold gauge  set to vacuum pump (7).
3) Operate vacuum pump,  and then open discharge 
side valve (Hi) (8) of manifold gauge set.
If there is no blockage in  the system, there will be an 
indication on high pressure gauge (9).
In this case, open the other side valve (Lo) (10) of 
the set and repair the system.
4) Approximately 10 minutes later, low pressure gauge  (11) should show a vacuum lower than –100 kPa (–
1.0 kg/cm
2, –760 mmHg, –14.7 psi) providing no 
leakage exists.
NOTE
• If the system does not show a vacuum  below –100 kPa (–1.0 kg/cm
2, –760 mmHg, 
–14.7 psi), close both valves, stop vacuum 
pump and watch movement of low 
pressure gauge.
• Increase in the gauge reading suggests  existence of leakage. In this case, repair 
the system before continuing its 
evacuation.
• If the gauge shows a stable reading  (suggesting no leakage), continue 
evacuation.
 
5) Evacuation should be carried out for a total of at  least 15 minutes.
6) Continue evacuation until low pressure gauge  indicates a vacuum less than –100 kPa (–1.0 kg/cm
2, 
–760 mmHg, –14.7 psi), and then close both valves.
7) Stop vacuum pump. Disconnect center charging  hose from pump inlet. No w, the system is ready for 
charging refrigerant.
Checking A/C System for Pressure Leaks
After completing the evacuation, close manifold gauge 
high pressure valve and low pressure valve and wait 10 
minutes. Verify that low pressure gauge reading has not 
changed.
CAUTION! 
If the gauge reading moves closer to “0”, 
there is a leak somewhere. Inspect the tubing 
connections and make necessary 
corrections. And then, evacuate system once 
again and make sure that there are no leaks.
 
7 5
2
4
1
10
11
3
9 8
6
I4RS0A720014-01  
Page 967 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-19
Charge
CAUTION! 
• Because the sight glass is not used for this A/C system, do not perform an additional 
charge to the A/C system. To charge the 
proper amount of refrigerant, recover and 
evacuate the A/C system first. And then, 
charge the proper amount of refrigerant 
into the A/C system.
• Always charge refrigerant through low  pressure side of A/C system after the initial 
charge is performed from the high 
pressure side with the engine stopped.
• Never charge refrigerant through high  pressure side of A/C system with engine 
running.
• Do not charge refrigerant while  compressor is hot.
• When installing tap valve to refrigerant  container to make a hole there through, 
carefully follow dire ctions given by 
manufacturer.
• A pressure gauge should always be used  before and during refrigerant charge.
• The refrigerant container should be  emptied of refrigerant  when discarding it.
• The refrigerant container should not be  heated up to 40  °C (104  °F) or over.
• Refrigerant container should not be  reversed in direction during refrigerant 
charge. Reversing in direction causes 
liquid refrigerant to enter compressor, 
causing troubles, such as compression of 
liquid refrigerant and the like.
 
NOTE
The air conditioning system contains HFC-
134a (R-134a).
Described here is a method to charge the air 
conditioning system with refrigerant from the 
refrigerant service container.
When charging refrigerant recovered by 
using the refrigerant and recycling 
equipment (when recycling refrigerant), 
follow the procedure described in the 
equipment manufacturer’s instruction 
manual.
 
Charge proper amount of refrigerant accurately in 
accordance with the following procedure.
Specified amount of refrigerant
370  ± 20 g (13.0 ± 0.7 oz)
The initial charge of the  A/C system is performed 
through the high pressure side with the engine stopped.
And next, this method must be followed by charging from 
the low pressure side with the engine running.
1) Check if hoses are routed properly after evacuating  the system.
2) Connect low charging hose (1) and high charging  hose (2) of the manifold gauge set (3) in position. 
Then, open refrigerant container valve (4) to purge 
the charging line.
3) Open the high pressure side valve (5) and charge  refrigerant to system.
4) After a while, open the low pressure side valve (6)  and close the high pressure side valve.
WARNING! 
Make sure that high pressure side valve is 
closed securely.
 
5) Start engine and keep engine speed at 1500 r/min, and then operate A/C system.
6) Charge A/C system with refrigerant in vapor state. At  this time, refrigerant container should be held 
upright.
1
2 6 3
5 4
I4RS0A720015-01  
Page 968 of 1496

Downloaded from www.Manualslib.com manuals search engine 7B-20 Air Conditioning System: Manual Type
7) When refrigerant container (1) is emptied, use the following procedure to replace it with a new 
refrigerant container.
a) Close low pressure valve.
b) Replace empty container with a refrigerant  container which has been charged with 
refrigerant. When using refrigerant container tap 
valve (2), use the following procedure for 
replacement.
i) Retract needle (3) and remove refrigerant container tap valve by loosening its plate nut 
(4).
ii) Install the refrigerant container tap valve to a  new refrigerant container.
c) Purge any air existing in center charging hose. When using refrigerant container tap valve, use 
the following procedure to purge air.
i) Once fully tighten refrigerant container tap valve (1), and then loosen (open) plate nut 
(2) slightly.
ii) Open low pressure side  valve (3) of manifold 
gauge set (4) a little.
iii) As soon as refrigerant comes out with a  “hiss” through a clearance between 
refrigerant container and tap valve, tighten 
plate nut as well as low pressure side valve.
iv) Turn handle of tap valve clockwise so that its  needle is screwed into the new container to 
make a hole for refrigerant flow. 8) After the system has been charged with specified 
amount (370 ±  20 g) of refrigerant or when low 
pressure gauge (1) and high pressure gauge (2) 
have indicated the following specified value, close 
low pressure side valve (3) on manifold gauge set 
(4).
Low side and high side pressure example
I2RH01720018-01
I2RH01720019-01
Gauges should read as  follows when ambient 
temperature is 30  °C (86  °F).
Pressure
on high pressure gauge 1590 – 1940 kPa
15.9 – 19.4 kg/cm
2
226 – 276 psi
Pressure
on low pressure gauge 270 – 430 kPa
2.7 – 4.3 kg/cm
2
38 – 61 psi
1
3 42
I4RS0A720016-01  
Page 969 of 1496

Downloaded from www.Manualslib.com manuals search engine Air Conditioning System: Manual Type 7B-21
Removal of Manifold Gauge Set
WARNING! 
High pressure side is under high pressure. 
Therefore, be careful not to get injured 
especially on your eyes and skin.
 
For the A/C system charged with the specified amount of 
refrigerant, remove manifold gauge set as follows:
1) Close low pressure side valve of manifold gauge set.  (The high pressure side valve is closed continuously 
during the process of charging.)
2) Close refrigerant container valve.
3) Stop engine.
4) Using shop rag, remove charging hoses from service  valves. This operation must be performed quickly.
5) Put caps on service valves.
Check A/C System for Refrigerant Leaks
Whenever a refrigerant leak is suspected in the system 
or any service operation has been performed which may 
result in malfunction of lines and connections, it is 
advisable to check for leaks.
Common sense should be used during refrigerant leak 
test, since the need and extent  of any such test will, in 
general, depend upon the nature of a complaint and the 
type of a service performed on the system.
Liquid leak detector
WARNING! 
• To prevent explosions and fires, make sure  that there are no flammables in the vicinity.
• When the refrigerant exposed to fire, it  turns into a poisonous gas (phosgene). Do 
not inhale this gas.
 
There is a number of fittings  and places throughout the 
A/C system where a liquid leak detector solution may be 
used to pinpoint refrigerant leaks.
By merely applying the solution to the area in question 
with a swab, such as attached to the cap of a vial, 
bubbles will form within seconds if there is a leak.
For confined areas, such as sections of the evaporator 
and condenser, an electronic (refrigerant) leak detector 
is more practical fo r determining leaks.
Special tool
(A):  09990–86012
Condenser Assembly On-Vehicle InspectionS7RS0B7216002
Check the followings.
• Clog of condenser fins If any clog is found, cond enser fins should be washed 
with water and should be dried with compressed air.
• Condenser fins for leakage and breakage If any defects are found, repair or replace condenser.
• Condenser fittings for leakage. If any defects are found, repair or replace condenser.
Condenser Assembly Removal and InstallationS7RS0B7216003
CAUTION! 
Do not damage condenser fins. If condenser 
fin is bent, straighten it by using flat head 
screwdriver or pair of pliers.
 
Removal
1) Recover refrigerant from A/C system referring to  “Operation Procedure for Refrigerant Charge”.
NOTE
The amount of removed compressor oil must 
be measured for replenishing compressor 
oil.
 
2) Remove front bumper referring to “Front Bumper and Rear Bumper Components in Section 9K”.
3) Disconnect discharge hose (1) and liquid pipe (2)  from condenser assembly (3).
4) Remove condenser assembly mounting bolts (4).
(A)
I5RS0C721006-01
4
1
3
2
I4RS0A720017-01