cooling system DAEWOO MATIZ 2003 Service Service Manual

Page 776 of 1184

7A–26 HEATING AND VENTILATION SYSTEM
DAEWOO M-150 BL2
D18A531B
Installation Procedure
1. Install the blower module with the nuts.
Tighten
Tighten the blower module retaining nuts to 3–5 Nm
(27–44 lb-in).
2. Connect the wiring harness.
3. Connect the blower motor connector. Refer to “Blow-
er Motor and Cooling Hose” in this section.
4. Install the blower resistor. Refer to “Blower Resistor”
in this section.
5. Install the evaporator on the vehicle equipped with
A/C. Refer to Section 7B, Manual Control Heating,
Ventilation, and Air Conditioning System.
6. Install the heater module–to–blower module connec-
tion tube on the vehicle not equipped with A/C. Refer
to “Heater Module” in this section.
7. Install the glove box to the instrument panel. Refer to
Section 9E, Instrumentation/Driver Information.
D108A532
DEFROSTER DUCT AND HOSES
(Left–Hand Drive Shown, Right–Hand
Drive Similar)
Removal Procedure
1. Remove the instrument panel. Refer to Section 9E,
Instrumentation/Driver Information.
2. Remove the defroster duct and hoses retaining
screws.
a. Retaining screw.
3. Remove the defroster duct and hoses.
b. Defroster duct and hoses.
D108A533
Installation Procedure
1. Install the defroster duct and hoses with the screws.
2. Install the instrument panel. Refer to Section 9E, In-
strumentation/Driver Information.

Page 783 of 1184

DAEWOO M-150 BL2

SECTION 7B
MANUAL CONTROL HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEM
CAUTION: Disconnect the negative battery cable before removing or installing any electrical unit or when a
tool or equipment could easily come in contact with exposed electrical terminals. Disconnecting this cable
will help prevent personal injury and damage to the vehicle. The ignition must also be in B unless otherwise
noted.
TABLE OF CONTENTS
Description and Operation 7B-2. . . . . . . . . . . . . . . . . .
System Components – Functional 7B-2. . . . . . . . . . .
Component Locator 7B-3. . . . . . . . . . . . . . . . . . . . . . . .
A/C System 7B-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic Information and Procedures 7B-5. . . . .
General Diagnosis 7B-5. . . . . . . . . . . . . . . . . . . . . . . . . . .
Testing the Refrigerant System 7B-5. . . . . . . . . . . . . .
Insufficient Cooling “Quick Check”
Procedure 7B-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure-Temperature Relationship
of R-134a 7B-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing the Refrigerant System 7B-7. . . . . . . . .
Air Conditioning System Diagnosis 7B-8. . . . . . . . . . . . .
Insufficient Cooling Diagnosis 7B-8. . . . . . . . . . . . . . .
Symptom Diagnosis 7B-11. . . . . . . . . . . . . . . . . . . . . . . .
Pressure Test Chart (R-134a System) 7B-11. . . . . . .
Repair Instructions 7B-13. . . . . . . . . . . . . . . . . . . . . . . .
On-Vehicle Service 7B-13. . . . . . . . . . . . . . . . . . . . . . . . .
General A/C System Service Procedures 7B-13. . . . . .
O-Ring Replacement 7B-13. . . . . . . . . . . . . . . . . . . . .
Handling Refrigerant 7B-13. . . . . . . . . . . . . . . . . . . . . .
Handling of Refrigerant Lines and Fittings 7B-13. . .
Maintaining Chemical Stability in the
Refrigeration System 7B-14. . . . . . . . . . . . . . . . . . .
Discharging, Adding Oil, Evacuating, and
Charging Procedures for A/C System 7B-14. . . . . Serviceable Components 7B-17. . . . . . . . . . . . . . . . . . . .
Control Assembly and Control Cables 7B-17. . . . . . .
Blower Motor and Cooling Hose 7B-17. . . . . . . . . . . .
Blower Resistor 7B-17. . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Motor Switch 7B-17. . . . . . . . . . . . . . . . . . . . . .
A/C Push Knob 7B-18. . . . . . . . . . . . . . . . . . . . . . . . . .
Receiver–Dryer and Dual Cut Switch 7B-18. . . . . . . .
Receiver–Dryer Bracket 7B-20. . . . . . . . . . . . . . . . . . .
Compressor 7B-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Condenser 7B-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A/C High Pressure Pipe Line 7B-22. . . . . . . . . . . . . . .
A/C Low Pressure Pipe Line 7B-25. . . . . . . . . . . . . . .
Evaporator Unit and Drain Hose 7B-26. . . . . . . . . . . .
Unit Repair 7B-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evaporator Core and Expansion Valve 7B-28. . . . . .
Compressor Overhaul 7B-29. . . . . . . . . . . . . . . . . . . . .
Specifications 7B-30. . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Specifications 7B-30. . . . . . . . . . . . . . . . . . . .
Fastener Tightening Specifications 7B-30. . . . . . . . . .
Special Tools and Equipment 7B-31. . . . . . . . . . . . . .
Special Tools Table 7B-31. . . . . . . . . . . . . . . . . . . . . . .
Schematic and Routing Diagrams 7B-32. . . . . . . . . .
A/C Diagrams 7B-32. . . . . . . . . . . . . . . . . . . . . . . . . . . .
A/C Airflow (Typical) 7B-33. . . . . . . . . . . . . . . . . . . . . .
A/C System (Typical) 7B-33. . . . . . . . . . . . . . . . . . . . .

Page 784 of 1184

7B–2 MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM
DAEWOO M-150 BL2
DESCRIPTION AND OPERATION
SYSTEM COMPONENTS
–FUNCTIONAL
Compressor
All compressors are belt–driven from the engine crank-
shaft through the compressor clutch pulley. The com-
pressor pulley rotates without driving the compressor
shaft until on electromagnetic clutch coils energized.
When voltage is applied to energize the clutch coil, the
clutch plate and hub assembly are drawn toward the
pulley. The magnetic force locks the clutch plate and
pulley together as one unit to drive the compressor
shaft.
Condenser Core
The condenser assembly in front of the radiator consists
of coils which carry the refrigerant and cooling fins that
provide the rapid transfer of heat. The air passing
through the condenser cools the high–pressure refriger-
ant vapor and cause it to condense into a liquid.
Expansion Valve
The expansion valve is located on the passenger
compartment side of the dash panel. The expansion
valve can fail in three different positions: open, closed,
or restricted. An expansion valve that fails in the open
position will result in a noisy A/C compressor or no cool-
ing. The cause can be a broken spring, a broken ball, or
excessive moisture in the A/C system. If the spring or
the ball is found to be detective, replace the expansion
valve. If excessive moisture is found in the A/C system,
recycle the refrigerant. An expansion valve that fails in
the closed position will result in low suction pressure and
no cooling. This may be caused by a failed power done
or excessive moisture in the A/C system. If the power
dome on the expansion valve is found to be defective,
replace the expansion valve. If excessive moisture is
found in the A/C system, recycle the refrigerant.
A restricted expansion valve will result in low suction
pressure and no cooling. This may be caused by debrisin the refrigerant system. If debris is believed to be
cause, recycle the refrigerant, replace the expansion
valve, and replace the receiver/dryer.
Evaporator Core
The evaporator is device which cools and dehumidifies
the air before it enters the vehicle. High–pressure liquid
refrigerant flows through the expansion tube (orifice)
and becomes a low–pressure gas in the evaporator. The
heat in the air passing through the evaporator core is
transferred to the cooler surface of the core, which cools
the air. As the process of heat transfer from the air to the
evaporator core surface is taking place, any moisture
(humidity) in the air condenses on the outside surface of
the evaporator core and is drained off as water.
Receiver–Dryer
The sealed receiver–dryer assembly is connected to the
evaporator outlet pipe. It acts as a refrigerant storing
container, receiving liquid and some vapor and refriger-
ant oil from the evaporator.
At the bottom the receiver–dryer is the desiccant, which
acts as a drying agent for the moisture that may have
entered the system. The receiver–dryer is serviceable
only as an assembly.
Dual Cut Switch
The dual cut switch controls compressor operation when
the cycling refrigerant pressure is dropped or surged.
Evaporator Thermistor
A semiconductor which resistance is noticeably changed
as the change of temperature. When the refrigerant tem-
perature of the evaporator drops to 0C (32F) and be-
low, the evaporator cores get stuck with frost or ice,
reducing the airflow, lowering the cooling capacity. The
thermistor is a sensor which is used to prevent from frost-
ing or icing.
The thermistor is installed on the evaporator.

Page 787 of 1184

MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM 7B–5
DAEWOO M-150 BL2
DIAGNOSTIC INFORMATION AND PROCEDURES
GENERAL DIAGNOSIS
TESTING THE REFRIGERANT
SYSTEM
If you suspect a problem in the refrigerant system,
check for the following conditions:
1. Check the outer surfaces of the radiator and the con-
denser cores to be sure that the airflow is not blocked
by dirt, leaves, or other foreign material. Check be-
tween the condenser and the radiator, as well as all
outer surfaces.
2. Check for restrictions or kinks in the condenser core,
the hoses, and the tubes.
3. Check the operation of the blower fan.
4. Check all the air ducts for leaks or restrictions. A low
airflow rate may indicate a restricted evaporator core.
5. Check for slippage of the compressor clutch.
6. Check the drive belt tension.
INSUFFICIENT COOLING “QUICK
CHECK” PROCEDURE
Perform the following “hand-feel” procedure to get a
quick idea of whether the air conditioning (A/C) system
has the proper charge of Refrigerant-134a.
1. Warm up the engine. Run the engine at idle.
2. Open the hood and all the doors.
3. Turn the A/C switch ON.
4. Set the temperature control to the full cold position.
5. Set the blower speed switch on 4.
6.“Hand-feel” the temperature of the evaporator outlet
pipe. The pipe should be cold.
7. Check for other problems. Refer to “Testing the Re-
frigerant System” in this section.
8. Leak check the system. Refer to “Leak Testing the
Refrigerant System” in this section. If you find a leak,
discharge the system and repair the leak as required.
After completing the repair, evacuate and charge the
system.
9. If there is no leak, refer to “Insufficient Cooling Diag-
nosis” in this section.

Page 790 of 1184

7B–8 MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM
DAEWOO M-150 BL2
AIR CONDITIONING SYSTEM DIAGNOSIS
INSUFFICIENT COOLING DIAGNOSIS
Step Action Value(s) Yes No
1Can you verify the customer complaint?–Go to Step 2System OK
2
1. Check the fuses Ef14, Ef19, and Ef12.
2. Check the blower fan operation.
3. Check the engine cooling fan operation.
4. Check the A/C compressor belt.
5. Check the A/C condenser for restricted air flow.
6. Check the slippage of the compressor clutch.
7. Repair or replace any components as needed.
8. Check the A/C system operation.
Is the A/C system operation normal?

System OKGo to Step 3
3
1. Turn the ignition switch OFF.
2. Connect the high and the low pressure gauges.
Are both pressures within the value specified?
Low SideGo to Step 8Go to Step 6
4Are both pressures above the specified value?Pressure:Go to Step 5–
5Are both pressures within the specified value?200 kPa
(29 Psi)Go to Step 8–
6Are both pressure below the specified value?
(29 Psi)
Go to Step 7Go to Step 4
7
1. Add the refrigerant R–134a.
2. Check the A/C system for leaks.
3. Repair any refrigerant leaks as needed.
4. Recover, evacuate, and recharge the A/C system.
Are both pressure within the specified value?High Side
Pressure:
1,500 kPa
(217.5 Psi)
Go to Step 8

8
1. Start the engine and allow it to run at idle.
2. Set the A/C controls to following positions.
The A/C switch to the ON position.
The fresh air control switch to fresh air.
The blower motor to 4.
The temperature to full cold.
Does the A/C compressor clutch engage?

Go to Step 9Go to Step 11
9
1. Check for a knocking noise from the A/C
compressor.
2. Cycle the A/C compressor ON and OFF in order
to verify the source of the noise.
Do you hear a loud knocking noise?

Go to Step 10Go to Step 14
10
1. Recover the A/C system refrigerant.
2. Replace the A/C compressor.
3. Evacuate and recharge the A/C system.
4. Check the A/C system for leaks.
Is the repair complete?

Go to Step 14

11
1. Turn the ignition switch OFF.
2. Disconnect the A/C compressor clutch coil
connector.
3. Connect a jumper wire from ground to one A/C
compressor clutch coil terminal.
4. Connect a fused jumper wire from the positive
battery terminal to the other A/C compressor
clutch coil terminal.
Does the A/C clutch engage?

Go to Step 12Go to Step 13

Page 791 of 1184

MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM 7B–9
DAEWOO M-150 BL2
Insufficient Cooling Diagnosis (Cont’d)
Step Action Value(s) Yes No
12
Repair the electrical circuit to the A/C compressor
clutch coil.
Does the A/C clutch engage?

Go to Step 20Go to Step 13
13Replace the A/C compressor clutch coil.
Does the A/C clutch engage?–Go to Step 9Go to Step 10
14
Important: Perform this test under garage condi-
tions; 21-32C (70-90F) and no sun load. Follow
this test carefully for accurate results.
1. Close all of the windows and the doors of the
vehicle.
2. Set the A/C controls to the following positions:
The A/C switch to the ON position.
The fresh air control switch to fresh air.
The blower motor to 4.
The temperature to full cold.
3. Start the engine and follow it to run at idle for
5 minutes.
4. Feel the evaporator inlet and outlet pipes.
Is there a noticeable difference in the temperature of
the evaporator inlet and outlet pipes?

Go to Step 16Go to Step 15
15
1. Recover the A/C system refrigerant.
2. Replace the expansion valve as needed.
3. Evacuate and recharge the A/C system.
4. Check the A/C system for leaks.
5. Note the discharge air temperature with the A/C
ON.
Is the discharge temperature normal?

Go to Step16Go to Step 18
16
Feel the liquid pipe between the condenser and the
expansion valve.
Is the pipe cold?

Go to Step 19Go to Step 17
17
1. Remove the restriction of the high pressure side.
2. Check the A/C system for leaks.
Is the repair complete?

System OK

18
1. Recover the A/C system refrigerant.
2. Evacuate and recharge the A/C system.
3. Check the A/C system for leaks.
Is the repair complete?

System OK

19
1. Run the engine at 3,000 rpm.
2. Close all of the windows and doors of the vehicle.
3. Set the A/C controls to the following positions:
The A/C switch to the ON position.
The fresh air control switch to fresh air.
The blower motor to 4.
The temperature to full cold.
4. Turn the A/C switch ON and OFF every
20 seconds for 3 minutes.
Are the A/C compressor high and the low side
pressures within the specified value of each other?
Low Side
Pressure:
200 kPa
(29 psi)
High Side
Pressure:
1,500 kPa
(217.5 psi)
System OKGo to Step 22

Page 792 of 1184

7B–10 MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM
DAEWOO M-150 BL2
Insufficient Cooling Diagnosis (Cont’d)
Step Action Value(s) Yes No
20
1. Turn the ignition switch OFF.
2. Turn the A/C switch to the OFF position.
3. Attempt to turn the clutch driver (not the pulley).
Can you turn the clutch driver freely by hand?

Go to Step 23Go to Step 21
21
1. Recover the A/C system refrigerant.
2. Replace the A/C compressor.
3. Evacuate and recharge the A/C system.
Is the repair complete?

System OK

221. Add the refrigerant R–134a.
Does the cooling performance improve?–System OKGo to Step 23
23
1. Recover the A/C system refrigerant.
2. Replace the compressor.
3. Evacuate and recharge the A/C system.
4. Check the A/C system for leaks.
Is the repair complete?

System OK

Page 794 of 1184

7B–12 MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM
DAEWOO M-150 BL2
Pressure Test Chart (R-134a System) (Cont’d)
Condition Related Symptons Probable Cause Correction

Suction Pressure
Abnormally High
Low pressure hose and
check joint are cooler
The expansion valve is
opened for too long.
Replace the expansion
valve.

Abnormally High

check joint are cooler
than the temperature
around the evaporator.

opened for too long.

valve.








Suction pressure is
lowered when the con-
denser is cooled by
water.



There is excessive
refrigerant in the system.



Recover, evacuate, and
recharge the system.
Suction and Dis-
charge Pressure Reduced airflow
through the condenser. The condenser or the
radiator fins are clogged. Clean the condenser and
the radiator.




Abnormally High







The radiator cooling fans
are not working properly.




Check the voltage and
the radiator cooling fan
rpm.
Check the fan direction.




Condenser is
excessively hot.

There is excessive
refrigerant in the system.

Recover, evacuate, and
recharge the system.



Suction and Dis-
charge Pressure
Abnormally Low


Low pressure hose and
metal end areas are
cooler than the
evaporator.


Clogged or kinked low
pressure hose.


Repair or replace the low
pressure hose.








Temperature around the
expansion valve is low
compared to that
around the
receiver/drier.



The high pressure line is
clogged.



Repair or replace the
high pressure line.


Refrigerant Leaks

The compressor clutch
is dirty.

The compressor shaft seal
is leaking.

Repair or replace the
compressor.
The compressor bolts
are dirty. Leaking around a
compressor housing bolt. Tighten the bolt(s) or
replace the compressor.



The compressor gasket
is wet with oil.

The compressor gasket is
leaking.

Repair or replace the
compressor.





Poor tightening in the
system.
Retighten the connection
(coupling, bolt etc.)
– O–ring is faulty. Replace the O–ring.

Page 799 of 1184

MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM 7B–17
DAEWOO M-150 BL2
SERVICEABLE
COMPONENTS
(Left–Hand Drive Shown, Right–Hand
Drive Similar)
CONTROL ASSEMBLY AND
CONTROL CABLES
To remove the control assembly and control cables, re-
fer to Section 7A, Heating and Ventilation System (With-
out Air Conditioning).
BLOWER MOTOR AND COOLING
HOSE
To remove the blower motor and cooling hose, refer to
Section 7A, Heating and Ventilation System (Without Air
Conditioning).
BLOWER RESISTOR
To remove the blower resistor, refer to Section 7A, Heat-
ing and Ventilation System (Without Air Conditioning).
BLOWER MOTOR SWITCH
To remove the blower motor switch, refer to Section 7A,
Heating and Ventilation System (Without Air Condition-
ing).

Page 812 of 1184

7B -- 30 MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM
DAEWOO M-150 BL2
SPECIFICATIONS
GENERAL SPECIFICATIONS 
 
Application
 
 
Unit
 
 
Description 
Compressor
 
--
 
SP--10.4PK 
 Receiver--Dryer
 
 --
 
 AL R/DRIER 
Refrigerant
 
Type
 
--
 
R--134a System 
 Refrigerant
 
 Capacity
 
 g
 
 500 (RHD : 530) 
RefrigerantOilinA/CSystem
 
Type
 
--
 
RL 244 PAG OIL RefrigerantOilinA/CSystem 
Capacity
 
cc
 
150 
 
A/C Cooling Capacity (Airflow rate 8.7 kg/min)
 
 
Kcal/h
 
 
5,500 
 Refrigerant Pressure in A/C Sys-
tem(Engine Idle, Fresh Air 30_C
(86_F)AmbientTemperature
 
 
Low Pressure Side
 
 
kPa (psi)
 
 
200 (2.9) 
 
 (86_F),AmbientTemperature
25_C--35_C(77_F--95_F), Tempera-
ture to Full Cold)
 
 
 High Pressure Side
 
 
 kPa (psi)
 
 
 1,500 (217.5) 
 
 
 A/C Compressor ON/OFF Condition
(Refer toSection 1F, Engine Controls
AbouttheA/CCompressorON/OFF
 
 
 
 Evaporator Therm-
istor Temperature
 
 
 
 _C(_F)
 
 
 
 
2.45(36.81)
1.0 (34.2)
ON
OFF
 
 
 
 
 
About theA/CCompressorON/OFF
Condition According to Engine Oper-
ating Status)
 
 
 
 
 
Dual Cut Switch
Pressure
 
 
 
 
 kPa
 
 
 
 
 
205--245
180--220
ON
OFF300--400
240--280
FASTENER TIGHTENING SPECIFICATIONS 
Application
 
NSm
 
Lb-Ft
 
Lb-In 
 
Compressor Upper Bracket Bolts
 
 
20
 
 
15
 
 
-- 
Compressor Front Head-to-Rear Head Through-Bolt
 
22
 
16
 
-- 
 High Pressure Pipe Line (Compressor→Condenser) Bolt
 
 23
 
 17
 
 -- 
High Pressure Pipe Line (Compressor→Condenser) Fitting
 
23
 
17
 
-- 
 High Pressure Pipe Line (Compressor→Condenser) Clamp Nut
 
 5
 
 --
 
 44 
Receiver--Dryer Flange Nut
 
14
 
10.5
 
-- 
High Pressure Pipe Line (Condenser→Receiver--Dryer) Fitting Nut
 
14
 
10.5
 
-- 
 
High Pressure Pipe Line (Receiver--Dryer→Evaporator) Fitting Nut
 
 
14
 
 
10.5
 
 
-- 
High Pressure Pipe Line(Receiver--Dryer→Evaporator) Clamp Nut
 
5
 
--
 
44 
 Low Pressure Pipe Line (Evaporator→Compressor) Fitting Nut
 
 14
 
 10.5
 
 -- 
Low Pressure Pipe Line (Evaporator→Compressor) Clamp Nut
 
5
 
--
 
44 
 Low Pressure Pipe Line(Evaporator→Compressor) Compressor Bolt
 
 23
 
 17
 
 -- 
Dual Cut Switch
 
13
 
--
 
11 5 
Receive--Dryer Bracket--to--Body Bolts
 
5
 
--
 
44 
 
Receive--Dryer Bracket Bolt
 
 
5
 
 
--
 
 
44 
Expansion Valve Coupling (Receiver--Dryer→Expansion Valve)
 
17
 
13
 
-- 
 Expansion Valve Coupling (Expansion Valve→Evaporator)
 
 22
 
 16
 
 -- 
Compressor Shaft Bolt
 
13
 
--
 
11 5 
 Condenser Mounting Nuts
 
 4
 
 --
 
 36

Page:   < prev 1-10 ... 11-20 21-30 31-40 41-50