Page 1536 of 2053

MANUAL & SEMIAUTO-HVAC 7C-7
SSANGYONG MY2002
DIAGNOSIS USING THE MANIFOLD GAUGE
On normal operation during the cooling cycle, the
manifold gauge must indicate approximately 1.5 - 2.0
kg/cm
2 at low pressure side and 14.5 - 15 kg/cm2 at
high pressure side, on condition that the temperature
at the cooler inlet, 30 ºC - 35 ºC, 2,000 rpm of the
engine rpm , full cold and maximum blower speed.
Cause Symptom
Action
1. High and low pressure are abnormally low.
2. Air at cooler outlet is not cold.
1. High and low pressure are abnormally high.
1. High and low pressure are abnormally high.
2. Connection at the low pressure is not cold.
There is a gas leak in the
cooling system.
Insufficient cooling and
faulty condenser cooling
by excessive
refrigerant.
Belt is slipped
There is an air in the
cooling system
Check the oil leak,
repair
Add the refrigerant
Keep the specified
amount of the
refrigerant, Clean the
condenser
Repair the belt
Clean and repair the
receiver-drier
Check the oil
contamination etc.
YAD7B070
YAD7B080
YAD7B100 YAD7B090
Page 1541 of 2053

SSANGYONG MY2002
7C-12 MANUAL & SEMIAUTO-HVAC
AIR CONDITIONER SYSTEM
DIESEL ENGINE
1 Compressor
2 High Pressure Hose
3 Condenser
4 Condenser Fan
5 Liquid Pipe (A)
6 Reveiver Drier
KAA7C030
7 Liquid (B)
8 Evaporator Assembly
9 Blower Unit
10 Heater Unit
11 Low Pressure Hose
Page 1542 of 2053

MANUAL & SEMIAUTO-HVAC 7C-13
SSANGYONG MY2002
GASOLINE ENGINE
1 Evaporator Assembly
2 Condenser Asembly
3 Screw-Hex SEMS (M8 x 1.5 x 35)
4 Fan & Shroud Assembly-Main
5 Fan & Shroud Assembly-Add
6 Supplement Assembly- c/ fan Mounting
7 Receiver & Bracket Assembly
8 Hose-Discharge
9 Bolt-Hex Sems (M8 x 1.25 x 30)
10 Hose Assembly-Suction11 Pipe Assembly-Suction
12 Pipe-Liquid-A
13 Pipe-Liquid-B
14 Resister-Condenser Fan
15 Clip-Closed-CT (M8)
16 Bolt-Hex FLG (M8 x 1.25 x 25)
17 Nut-Hex (M6 x 1.0)
18 Screw-Hex SEMS (M6 x 1.0 x 25)
19 Screw-Hex SEMS (M6 x 1.0 x 16)
KAA7C040
Page 1545 of 2053

SSANGYONG MY2002
7C-16 MANUAL & SEMIAUTO-HVAC
Charging Refrigerant
Charging for Gas
1. Connect the tap valve to the refrigerant tank.
2. Open the low pressure and adjust the low-side
reading below 4.2 kg/cm
2.
3. Place the refrigerant tank in the warm water
(40 °C) and keep the gas pressure in the refrigerant
tank higher than the gas pressure in the charging
valve.
4. Run the engine at high speed and operate A/C
system.
Notice: Place the refrigerant tank on the flat floor
to protect the liquid refrigerant from coming
through the suction inlet resulting in the
compressor’s damage.
5. Charge the specified amount to the charging valve
and close the low pressure valve.
Notice:
If the charging speed is low, it’s more efficient
to place the refrigerant tank in the warm water
(40 °C). But the temperature should keep below
(52 °C) at any situation.
Be careful not to contact the heating device or
material.
Charging for Liquid
Notice:
Do not operate when charging the system through
the high-side rpessure.
Do not open the low pressure valve when charging
the system by the liquid refrigerant.
1. Tighten both high pressure and low pressure
completely before evacuating the charging valve.
2. Connect the tap valve of the refrigerant tank.
3. Open the high pressure valve and turn the
refrigerant tank upside down.Single: 850 ± 50 g
Dual: 1200 ± 50 g
Specified amount
YAD7B210
YAD7B220
YAD7B230