ISUZU AXIOM 2002  Service Workshop Manual HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
1A±25
Checking The Refrigerant System With Manifold Gauge
Since Refrigerant-134a (HFC-134a) is used in the air
conditioning system in this vehicle, be

Page 52 of 2100

ISUZU AXIOM 2002  Service Workshop Manual 1A±26
HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
Connect The Manifold Gauge
Low-pressure hose (LOW) Ð Suction side
High pressure hose (HI) Ð Discharge side
901R100020
Legend
(1) Low Side
(2)

Page 53 of 2100

ISUZU AXIOM 2002  Service Workshop Manual HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
1A±27
ConditionPossible causeCorrection
Discharge (High Gauge) Pressure
Abnormally High
Condenser clogged or dirty.Clean the condenser fins
Abnormally

Page 54 of 2100

ISUZU AXIOM 2002  Service Workshop Manual 1A±28
HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
Condition CorrectionPossible cause
Suction (Low Gauge) Pressure
Abnormally Low
Receiver/drier inlet and outlet
refrigerant line temperature. (A

Page 55 of 2100

ISUZU AXIOM 2002  Service Workshop Manual HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
1A±29
Condenser Fan Diagnosis
While the air conditioning is ON, the cycling switch in the
triple pressure switch senses the refrigerant pressure,
and

Page 56 of 2100

ISUZU AXIOM 2002  Service Workshop Manual 1A±30
HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
Chart ªAº Condenser Fan Does Not Run 
StepActionYe sNo
1Are 30A fuse normal?Go to Step 2Replace
2Is relay (X-16) normal?Go to Step 3Replace
3I

Page 57 of 2100

ISUZU AXIOM 2002  Service Workshop Manual HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
1A±31
Air Conditioning System
Individual Inspection
Triple Pressure Switch (V6, A/T)
1. Disconnect the connector and check for continuity
between pres

Page 58 of 2100

ISUZU AXIOM 2002  Service Workshop Manual 1A±32
HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
Repair Of Refrigerant Leaks
Refrigerant Line Connections
Install new O-rings, if required.  When disconnecting or
connecting lines, use two wren

Page 59 of 2100

ISUZU AXIOM 2002  Service Workshop Manual HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
1A±33
Leak Check
Inspection of refrigerant leak
Refrigerant leak may cause an adverse effect not only on
the performance and durability of each compon

Page 60 of 2100

ISUZU AXIOM 2002  Service Workshop Manual 1A±34
HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
3. If the leak is still present, discharge and recover the
refrigerant from the system.
4. Replace the O-rings.
O-rings cannot be reused. Alway